Feed water heating combined circuit and reasons
Short answer
Circuit: gas turbine with regenerator preheating compressed air; remaining exhaust heats feed water in a gas-to-water heater before the fired steam boiler, replacing bled-steam heaters. Reasons: exhaust carries 60-70% of fuel energy, giving 50-60% overall efficiency, lower fuel cost and emissions, lower capital cost, fast start, less cooling water, and repowering old steam plants.
In a combined gas and steam turbine power plant, exhaust gases of regenerative gas turbine is used to heat feed water for the boiler of a steam power plant. According to this concept draw a complete circuit of a combined power plant showing "Heating feed water with exhaust gases". What are the reasons that inspire you to construct a combined cycle power plant?
Circuit: heating feed water with exhaust gases
The gas turbine is regenerative: its exhaust first preheats the compressed air in a regenerator, and the remaining exhaust heat heats the boiler feed water.
air 1 fuel
v v
[C]-2->[ Regen ]-x->[ CC ]-3->[GT]==> G1
^ | | 4
+---|------------------+
v y exhaust
stack <-- +------------------+
| Feed water heater|<--d--+
+------------------+ |
| e hot water +------+
v | Pump |
fuel --> +--------------+ a +------+
| Steam boiler |--+ ^ c
+--------------+ v |
[ST]==>G2 |
| b |
v |
[Condenser]--+
- Compressed air (2) is preheated by the turbine exhaust in the regenerator (x), heated in the combustion chamber (3) and expanded in the gas turbine (4).
- Exhaust leaving the regenerator (y), still at about 300-400 C, flows through the feed water heater and then to the stack.
- Condensate pumped from the condenser (d) is heated by this gas to state e and enters the fired steam boiler, which produces superheated steam (a) for the steam turbine.
- Since bled-steam heaters are no longer needed, more steam expands fully in the turbine, increasing steam plant output with the same boiler fuel.
Reasons for building a combined cycle plant
- Gas turbine exhaust (450-600 C) carries 60-70% of fuel energy; using it gives overall efficiency of 50-60%.
- Lower fuel cost and CO2 per kWh; lower emissions with natural gas.
- Lower capital cost and shorter construction time than coal or nuclear plants; phased installation possible.
- Fast start and load-following, useful for varying demand.
- Less cooling water and space than a steam plant of the same output.
- Old steam plants can be repowered by adding a gas turbine.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Combined plant heating feed water with exhaust · Power Plant Equipment, chapter 8 · asked 2×
- Waste heat methods and feed water heating layout · Power Plant Equipment, chapter 8 · asked 2×
- Regenerative scheme with open feed water heater · Power Plant Equipment, chapter 7
- Working of combined gas-steam plant · Power Plant Equipment, chapter 8
- Regenerative gas turbine: 1 to 6.9 bar · Power Plant Equipment, chapter 6
- Reheat gas turbine power plant · Power Plant Equipment, chapter 6
- Combined cycle gas turbine versus hydro · Power Plant Design, chapter 1
- Boiler trial heat balance sheet · Applied Thermodynamics, chapter 1
- Boiler efficiency with superheated steam · Applied Thermodynamics, chapter 1
- Gas turbine 60 MW: heat loss and areas · Fundamental of Thermodynamics & Heat Transfer, chapter 4