- Asked 3/22
- 2082 Baisakh · 6 marks
- 2074 Chaitra · 8 marks
- 2076 Chaitra · 8 marks
Dynamic response of excitation system
Short answer
Dynamic response is governed by loop gain and time constants. Closed loop is G/(1+G) with G=K/[(1+sTA)(1+sTE)(1+sTG)]. Steady-state error is 1/(1+K); high K improves accuracy but may cause instability, so stabilizing feedback adds damping.
Explain the dynamic response of excitation system with suitable mathematical deduction.
The dynamic response of an excitation system is how fast and how smoothly the generator terminal voltage follows a change in reference voltage (or recovers after a load change). It depends on the gains and time constants of the amplifier, exciter and generator field, and on stabilizing feedback.
Mathematical model
Basic AVR loop (sensor time constant neglected, unity feedback):
Vref + Ve +-------+ +-------+ +-------+
--->(+)----->| KA |-->| KE |-->| KG |--+--> Vt
^ - |1+sTA | |1+sTE | |1+sTG | |
| +-------+ +-------+ +-------+ |
+-------------------------------------------+
Open-loop transfer function:
Closed loop:
Steady-state response
For a step , using the final value theorem:
To keep the voltage error small (e.g. below 1 %), must be large (about 100 or more).
Transient response and stability
Characteristic equation:
By the Routh criterion, the system is stable only if
So a large (good accuracy) makes the response more oscillatory and can make it unstable. This is the basic conflict in AVR design.
Vt
high K: fast but oscillatory
| .-.
| / '-.__.-------------
| / ___.-------------- low K
| / _.-' (slower, larger error)
|/.'
+---------------------------> t
Improving the dynamic response
- Stabilizing (rate) feedback from exciter output to amplifier input, : adds damping only during transients, leaving steady-state gain unchanged. Closed loop becomes
- Fast exciters (static thyristor or brushless) with small , and high ceiling voltage and response ratio, so the field current can be forced quickly.
- Lead-lag compensation or a power system stabilizer (PSS) for damping rotor oscillations.
A good excitation system gives a fast rise, small overshoot, short settling time and a small steady-state voltage error.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Need for excitation and improving dynamic response · Power Plant Equipment, chapter 3
- Excitation system with stabilizing transformer: transfer function · Power Plant Equipment, chapter 3 · asked 13×
- Function of excitation system and its transfer function · Power Plant Equipment, chapter 3 · asked 2×
- Brush excitation system · Power Plant Equipment, chapter 3
- Static excitation system · Power Plant Equipment, chapter 3
- Static vs dynamic mathematical model · Simulation and Modeling, chapter 2 · asked 3×
- Dynamic mathematical model with example · Simulation and Modeling, chapter 2 · asked 2×
- Dynamic characteristics: rise time, delay, response · Instrumentation and Measurement, chapter 4
- Effect of feedback on dynamic response · Control Systems, chapter 1