Comparing systems of traction electrification

Short answer

Electrification systems: DC (600-3000V, series motors, many substations, urban), single-phase AC (25kV 50Hz, light overhead, few substations, mainline), three-phase AC (3.3kV, induction motors, complex overhead, obsolete), composite (single-phase to DC or three-phase on locomotive). DC has high starting torque but high substation cost; 25kV AC is standard for mainlines with low line cost but telecom interference.

Compare the characteristics of various system of electrification for traction purpose.

Systems of track electrification are classified by the type of supply fed to the train: DC system, single-phase ac system, three-phase ac system and composite systems (single-phase to dc, or single-phase to three-phase on the locomotive).

1. DC system (600–750 V, 1500 V, 3000 V)

  • DC series motors fed through third rail or overhead line; substations with rectifiers every 3–5 km (low voltage) or 15–30 km (3 kV).
  • High starting torque, simple and light motors, good for frequent stops.
  • Used for tramways, metro and suburban services.

2. Single-phase low-frequency ac (15–16 kV, 16⅔ or 25 Hz)

  • AC series motors with tap-changing transformer on the locomotive.
  • Needs special low-frequency generation or frequency converters.
  • Used on older main lines in Europe.

3. Three-phase ac (3.3–3.6 kV, 16⅔ Hz)

  • Three-phase induction motors; two overhead wires plus rail.
  • Simple robust motors, automatic regeneration, but complex overhead and nearly constant speed.
  • Used on some hill railways; now obsolete.

4. Composite systems

  • Single-phase to dc (25 kV, 50 Hz): a transformer and rectifier on the locomotive feed dc series motors. Cheap single overhead wire at high voltage, substations 40–50 km apart, supply from the national grid at 50 Hz. The most widely used main-line system today (India, many countries).
  • Single-phase to three-phase: phase/frequency converter or VVVF inverter on board feeding induction motors. Modern locomotives use this.

Comparison

PointDC1-ph ac (25 kV, 50 Hz)3-ph ac
Line voltage0.6–3 kV25 kV3.3–3.6 kV
OverheadHeavy conductorLight single wireTwo wires, complex
Substation spacing3–30 km40–50 kmMedium
MotorDC seriesDC series via rectifier / inductionInduction
Starting torqueHighHighModerate (high with VVVF)
Speed controlEasyEasyDifficult (fixed)
RegenerationPossible (needs control)PossibleNatural
InterferenceLowHigh (telecom lines)Moderate
Initial costHigh (substations)LowHigh
UseMetro, urbanMain lineHill sections (old)