Electronic automatic voltage regulator

Short answer

An electronic AVR is a closed-loop PID controller that rectifies terminal voltage, compares it with a stable reference, and adjusts thyristor firing angle to control exciter field. Limiters and stabilising feedback prevent hunting and overheating.

Describe the working principle of electronic based automatic voltage regulator with suitable diagrams.

An electronic automatic voltage regulator (AVR) keeps the generator terminal voltage at the set value by measuring it continuously and adjusting the field current through power-electronic switches (thyristors or transistors), with no moving parts.

Principle

It is a closed-loop (feedback) control system. The error between the reference voltage VrefV_{ref} and the measured voltage VtV_t is amplified and used to change the exciter field:

Efd=KA (Vref−Vt+Vs)E_{fd} = K_A\,(V_{ref} - V_t + V_s)

where KAK_A is the amplifier gain and VsV_s is the signal from the stabiliser (PSS). If VtV_t falls (for example, when load increases), the error rises, the field current increases and the voltage comes back.

Block diagram

 Vref -->( + )--> Amplifier -> Firing -> Thyristor
           ^ -     (PID)        circuit   bridge
           |                                 |
           |                                 v
           |                          Exciter / field
           |                                 |
        Rectifier                            v
        & filter <------- PT <------- Generator Vt
           ^
     Stabilising feedback / limiters

Main parts and their work

  1. Sensing (PT + rectifier + filter): steps down the terminal voltage, rectifies and smooths it into a DC signal proportional to VtV_t. Often the reactive current from a CT is added (load compensation/droop) so parallel units share vars.
  2. Comparator (error detector): compares the sensed signal with a stable reference (zener or digital set-point).
  3. Amplifier / controller: op-amp or digital PID amplifies the error.
  4. Firing circuit: converts the control voltage into a firing angle α\alpha for the thyristors. Smaller α\alpha gives more field voltage, since Vdc=1.35 Vaccos⁡αV_{dc} = 1.35\,V_{ac}\cos\alpha for a full bridge.
  5. Power stage: thyristor bridge feeding the exciter field (brushless) or main field (static).
  6. Stabilising feedback: rate feedback from the field voltage, or a PSS, damps hunting and oscillations.
  7. Limiters and protection: over-excitation limiter, under-excitation limiter, V/Hz limiter, stator current limiter.

Operation

  • Steady state: firing angle fixed, Vt=VrefV_t = V_{ref}.
  • Load increases or lagging power factor: VtV_t drops, error positive, α\alpha decreases, field current rises, VtV_t restored.
  • Load rejection: VtV_t rises, α\alpha increases (or inverts), field reduced.

Modes

  • Auto mode: voltage control as above.
  • Manual mode: field current control, used for testing or when the PT fails.

Advantages over electromechanical regulators

  • Fast response with no dead band.
  • No moving contacts, so little maintenance.
  • Accurate regulation (about ±0.5 %).
  • Easy to add limiters, PSS and remote control.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Power Plant Design chapter 4 questions →