Short answer

True. A pure derivative controller produces zero output for constant error, cannot eliminate steady-state error, and amplifies high-frequency noise. It is always combined with proportional and/or integral control (PD/PID) to provide corrective action and damping.

State whether the statement "Derivative controllers are always used with other controllers" is true or false and justify your answer.

True. A derivative (D) controller is never used alone; it is always combined with a proportional and/or integral controller, as PD or PID.

Justification

A derivative controller gives an output proportional to the rate of change of the error:

u(t)=Kdde(t)dt,Gc(s)=Kdsu(t)=K_d\frac{de(t)}{dt},\qquad G_c(s)=K_ds
  1. No action on constant error: if the error is constant (even large), de/dt=0de/dt=0, so the controller output is zero. A steady error is never corrected, so D alone cannot hold the output at the set point.
  2. Blocks DC signals: Gc(0)=0G_c(0)=0. In the loop it acts like a zero at the origin, which can cancel the plant's integrator and reduce the system type, so the steady-state error grows.
  3. Noise amplification: ∣Gc(jω)∣=Kdω|G_c(j\omega)|=K_d\omega rises with frequency, so high-frequency noise is amplified strongly. With a P term the useful low-frequency action dominates.
  4. Anticipatory, not corrective: D action predicts the error trend and adds damping; it only improves the transient part of the response.

How it is used

With proportional action (PD):

Gc(s)=Kp+Kds=Kp(1+Tds)G_c(s)=K_p+K_ds=K_p(1+T_ds)
  • The P part removes and holds the error.
  • The D part adds a zero, increases damping, reduces overshoot and settling time, and improves stability.
ControllerSteady error correctionDamping / overshoot
D alonenoneimproves
PDyes (P)improves
PIDeliminated (I)improves

Example: in a position servo, a PD controller lets the motor slow down as it nears the target (D) while still pushing it there (P). A pure D controller would stop acting once the motor is at rest away from the target.

✓ Answer checked by Claude Opus 5.5 (high effort)