- 2070 Chaitra · 12 marks
Lag compensator for K/[s(s+4)(s+80)], Kv = 30
Short answer
K=9600; lag compensator Gc(s)=(1+2.19s)/(1+9.50s) shifts the gain crossover to 4.56 rad/s. This achieves Kv=30 s⁻¹ and a phase margin of 33.6°.
Design series lag compensator for the unity feedback system with feedforward transfer function G(s) = K/[s(s+4)(s+80)]. The velocity error constant is 30 s⁻¹ and phase margin at least 33°.
A lag compensator () is designed with the Bode plot method: the gain is fixed by , and the lag network lowers the high-frequency gain so the crossover moves to a frequency with enough phase margin.
Step 1: Gain for
Step 2: Uncompensated margins
- Gain crossover: at rad/s; , so .
- Phase crossover: rad/s, dB.
The PM is far below .
Step 3: New gain crossover frequency
Allow for the lag of the compensator at the new crossover. Required plant phase:
Step 4: Value of
At 4.56 rad/s:
The lag network must reduce the gain by this amount: .
Step 5: Corner frequencies
Place the zero one decade below the new crossover:
Step 6: Compensator and check
| Quantity | Uncompensated | Compensated |
|---|---|---|
| Gain crossover | 10.55 rad/s | 4.57 rad/s |
| Phase margin | 13.3° | 33.6° |
| Gain margin | 8.9 dB | 20.9 dB |
| 30 s | 30 s |
The lag network adds only at the new crossover, within the allowed.
Answer: , ; and .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Lag compensator for 2/[s(s+1)(s+2)], Kv = 5, PM 40° · Control Systems, chapter 7 · asked 2×
- Lag compensator for 0.53/[s(1+s)(1+0.5s)], Kv = 5 · Control Systems, chapter 7
- Lag compensator for 1.06/[s(s+1)(s+2)], ramp error < 0.2 · Control Systems, chapter 7
- Transfer function with G3 feedforward, H1 and unity loop · Control Systems, chapter 3
- Lag compensator for 1/[s(s+1)(0.5s+1)], Kv = 5 · Control Systems, chapter 7
- Lag compensator for k/[s(1+0.1s)(1+0.2s)], Kv = 30 · Control Systems, chapter 7 · asked 4×
- Short note: Phase-lead/phase-lag compensator · Digital Control System, chapter 4
- Bode design: PM 55°, GM 10 dB, Kv = 5 · Digital Control System, chapter 4
- Design: 120 m head plant, 33 kV · Power Plant Design, chapter 4 · asked 3×
- Series programming of a third-order transfer function · Digital Control System, chapter 4 · asked 2×