- 2071 Chaitra · 4 marks
Angle and magnitude criteria for k/[(s+1)(s+3)]
Short answer
Yes, the point lies on the locus because the angle criterion gives -180° (sd is on the vertical line σ=-2). The required gain from the magnitude criterion is k = |sd+1|·|sd+3| = 13.25.
For the unity feedback system with open loop transfer function (OLTF) G(s) = k/[(s+1)(s+3)], use angle criteria to check whether the root locus passes from point sd = −2 + j3.5. If yes, use magnitude criteria to select the appropriate value of gain parameter.
Angle criterion
The locus passes through only if .
| Vector | Value | Angle |
|---|---|---|
The angle criterion is satisfied, so the root locus passes through . This is expected: for two real poles, the complex part of the locus is the vertical line through their midpoint, .
Magnitude criterion
Check
With : , so . ✓
Answer: Yes, the point lies on the root locus. The required gain is k = 13.25.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Checking whether root locus passes through point P · Control Systems, chapter 5
- Root locus criteria; poles 0, −1±j2 · Control Systems, chapter 5
- Root locus: poles −2±j3, zero at origin · Control Systems, chapter 5
- Root locus with poles 0, −6, −2 ± j3 · Control Systems, chapter 5
- Transfer function with G3 feedforward, H1 and unity loop · Control Systems, chapter 3
- Criteria for a point to lie on root locus · Control Systems, chapter 5
- Root locus of a sampled system (T = 0.5 s) · Digital Control System, chapter 4
- Root-locus design: ζ = 0.5, ts = 2 s, plant 1/(s(s+2)) · Digital Control System, chapter 4 · asked 5×
- Root-locus design: ζ = 0.5, ts = 2 s, plant 1/(s(s+1)) · Digital Control System, chapter 4 · asked 5×
- Root-locus design: 8 samples per cycle, T = 0.2 s · Digital Control System, chapter 4