Diverter resistance for flat compound generator
Short answer
Extra field ampere-turns needed = 0.2×1000 = 200 AT. Series field current required 200/4 = 50 A. Diverter carries 80−50 = 30 A. Diverter resistance = (50×0.05)/30 = 0.0833 Ω.
A long shunt compound generator has a shunt field winding of 1000 turns per pole, series field winding of 4 turns per pole and resistance of . In order to obtain the rated voltage both at no load and full load for operation as shunt generator, it is necessary to increase field current by 0.2 A. The full load armature current of compound generator is 80 A. Calculate the diverter resistance connected in parallel with series field to obtain flat compound operation.
For flat compounding, the series field must supply the extra field ampere-turns that a shunt generator needs to keep the voltage constant from no load to full load. A diverter in parallel with the series field passes the surplus armature current.
Ia +----[Rd]----+
---->--------+ +----+---> to load
+--[ Rse ]---+ |
Ise Rsh (across load)
Step 1: Extra ampere-turns needed
Step 2: Series field current required
Step 3: Diverter current
In a long shunt machine the series field (with its diverter) is in the armature circuit, so the full-load armature current of 80 A divides between the series field and the diverter:
Step 4: Diverter resistance
The diverter and series field are in parallel, so their voltage drops are equal:
Answer: diverter resistance .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Long shunt compound generator speed, lap and wave · Electrical Machines, chapter 3 · asked 2×
- Long shunt compound generator speed, 300 conductors · Electrical Machines, chapter 3 · asked 2×
- EMF of long shunt compound generator · Electrical Machines I, chapter 3 · asked 2×
- Long shunt compound generator emf, 40 A at 200 V · Electrical Machines, chapter 3
- Compound generator emf, long and short shunt · Electrical Machines, chapter 3
- EMF and load resistance of short shunt compound generator · Electrical Machines I, chapter 3
- Long shunt compound generator speed · Electrical Machine, chapter 3
- Starting shunt generator on no load and voltage build-up · Electrical Machines I, chapter 3
- EMF of short shunt compound generator (0.5 Ω armature) · Electrical Machines I, chapter 3 · asked 2×
- Short shunt compound generator, 100 A · Electrical Machine, chapter 3