Need of starter and four-point starter
Short answer
A starter limits the huge armature current at standstill, when Eb=0 makes Ia=V/Ra. The four-point starter connects the no-volt coil directly across the supply through a protective resistance, independent of field current, so field control does not cause false tripping. It provides no-voltage and overload protection.
Explain the need of starter in a DC motor and describe the working principle of 4 point starter with a neat sketch.
Need for a starter
In a DC motor . At start the speed is zero, so and . Since is very small (e.g. 0.5 Ω), a 220 V motor would draw about 440 A, many times rated current. This would burn the winding, cause heavy sparking at the commutator, give a damaging torque jerk and a dip in supply voltage. A starter puts a resistance in series with the armature at start and cuts it out step by step as builds up. It also gives no-voltage and overload protection.
Four-point starter
It has four terminals: L (line), A (armature), F (field) and N (no-volt coil return to supply). The key change from a three-point starter is that the no-volt coil (NVC) is connected directly across the supply through a protective resistance, not in series with the field.
L o--[OLR]--o pivot/handle
\
studs 1 2 3 4 5 ... ON
o-R-o-R-o-R-o-R-o
| F o---- shunt field
A o---- armature (brass arc from stud 1)
[NVC]--[R protective]--o N ---- supply (-)
Working
- The handle is moved from OFF to stud 1. Current divides into three parallel paths: (a) armature through the full starting resistance, (b) shunt field through the brass arc, getting full voltage, and (c) the NVC with its protective resistance, across the supply.
- As speed rises, increases; the handle is moved stud by stud, cutting out the starting resistance.
- At the ON position the armature is connected straight to the supply and the NVC holds the handle against its spring.
Protections
- No-voltage release: if supply fails, the NVC is de-energised and the spring returns the handle to OFF.
- Overload release (OLR): on excess current the OLR attracts its armature and shorts the NVC, releasing the handle.
Why four-point
In a three-point starter the NVC carries field current. When a large field regulator resistance is used to raise speed, field current falls, NVC becomes weak and the handle may release while the motor is running. In a four-point starter the NVC current does not depend on field current, so field control over a wide range is possible without false tripping.
Drawback: if the field circuit opens, the NVC still holds the handle, so there is no protection against over-speeding due to field failure.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Need of DC motor starter and three-point starter · Electrical Machines I, chapter 4 · asked 4×
- DC motor working principle and torque equation · Electrical Machines I, chapter 4 · asked 4×
- Need of starter and induction motor starting methods · Electrical Machines I, chapter 5
- DC motor principle and role of commutator and brushes · Electrical Machines I, chapter 4
- Construction and working of 3-phase induction motor · Electrical Machines I, chapter 5
- Working of 3-point DC motor starter · Electrical Machines, chapter 4 · asked 2×
- Three terminal DC motor starter · Electrical Machine, chapter 4
- DC motor working principle and torque equation · Electrical Machines, chapter 4 · asked 2×
- High starting current; 3-point starter · Electrical Machines, chapter 4 · asked 4×