- 2082 Kartik (new course) · 6 marks
Need of starter and induction motor starting methods
Short answer
At start, high inrush current (5–7× FL) can cause voltage dips and winding stress. Starters limit current: DOL for small motors; auto-transformer and star-delta reduce voltage; rotor resistance for slip-ring motors gives high torque; soft starters/VFDs provide smooth control.
Explain why do we need a starter to start an induction motor? Also explain different methods of induction motor starting.
A starter is a device that limits the starting current of an induction motor and gives overload and no-volt protection.
Why a starter is needed
At standstill, slip , so the rotor behaves like a short-circuited transformer secondary. The rotor emf is maximum and the only opposition is the small leakage impedance:
The stator draws 5–7 times full-load current at rated voltage. This causes:
- a large voltage dip in the supply line, disturbing other loads;
- heating and mechanical stress on the windings;
- tripping of protective devices.
Small motors (below about 5 kW) can be started direct-on-line; larger ones need a starter that reduces the voltage or adds rotor resistance during starting.
Starting methods
1. Direct-on-line (DOL) starter — full voltage applied through a contactor with overload relay. Simple and cheap; starting current 5–7 × FL. Used for small motors.
2. Stator resistance (reactor) starting — resistors in series with each stator phase reduce the voltage to . Current falls to times, but torque falls to times. Resistors are shorted after run-up. Wasteful; used rarely.
3. Auto-transformer starting — a 3-phase auto-transformer applies a tapped voltage . Motor current falls to times, line current to times, starting torque to times. Better than resistance starting; used for large motors.
4. Star–delta starting — for motors designed to run in delta. At start the winding is connected in star, so each phase gets ; after speed builds up it is switched to delta.
Cheap and common for medium squirrel-cage motors.
Supply ---[TPDT switch]--- Stator
Start: Y Run: Delta
5. Rotor resistance starting (slip-ring motors only) — external resistance in the rotor via slip rings reduces starting current and, by increasing towards 1, increases the starting torque. Resistance is cut out in steps as the motor speeds up.
6. Soft starter / VFD — thyristor (or inverter) control raises voltage (or frequency) smoothly. Low current, smooth acceleration; used in modern installations.
| Method | Motor type | Start current | Start torque |
|---|---|---|---|
| DOL | Cage (small) | 5–7 × FL | High |
| Auto-transformer | Cage | × DOL | × DOL |
| Star–delta | Cage (delta-run) | 1/3 × DOL | 1/3 × DOL |
| Rotor resistance | Slip ring | Low | High |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Need of DC motor starter and three-point starter · Electrical Machines I, chapter 4 · asked 4×
- Need of starter and four-point starter · Electrical Machines I, chapter 4
- Starting, no-load and full-load current of slip ring motor · Electrical Machines I, chapter 5
- Starting current and rotor resistance for 150 kW slip ring motor · Electrical Machines I, chapter 5
- Torque of 4-pole induction motor at 1400 rpm · Electrical Machines I, chapter 5
- DC series motor for starting heavy loads · Electrical Machines I, chapter 4
- DFRT, starting methods and capacitor start-run motor · Electric Machines II, chapter 3
- Starting line current of capacitor start motor · Electric Machines II, chapter 3
- Soft start variable AC voltage starter · Utilization of Electrical Energy, chapter 3
- High starting current; 3-point starter · Electrical Machines, chapter 4 · asked 4×