- 2078 Kartik · 6 marks
Starting line current of capacitor start motor
Short answer
At starting, capacitor reactance Xc = 1/(2π×50×12e-6) = 265.26 Ω. Main current Im = 230/(15+j22.5) = 8.505∠−56.31° A, auxiliary current Ia = 230/(50+j(120−265.26)) = 1.497∠71.01° A. Line current = Im + Ia = 7.69∠−47.4° A, power factor 0.677 lagging.
The equivalent impedances of the main and auxiliary windings in a single-phase capacitor start motor are (15 + j22.5) Ω and (50 + j120) Ω respectively, while the capacitance of the capacitor is 12 μF. Determine the line current at starting on a 230 V, 50 Hz supply.
At starting both windings are across the 230 V supply. The capacitor is in series with the auxiliary winding. Line current is the phasor sum of the two winding currents.
Given: , , , V, Hz.
Capacitive reactance
Branch impedances
Winding currents
Line current
Phase angle between and ; starting power factor lagging.
I_a (1.50 A, +71.0 deg)
^
|
-------+--------------> V
| \
| \ I_L (7.69 A, -47.4 deg)
| \
v I_m (8.51 A, -56.3 deg)
Answer: starting line current A, i.e. 7.69 A at 0.677 lagging power factor.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- DFRT, starting methods and capacitor start-run motor · Electric Machines II, chapter 3
- Split phase motor added resistance and capacitance · Electric Machines II, chapter 3
- Split-phase motor winding currents at starting · Electric Machines II, chapter 3
- Starting capacitor and change in starting torque · Electric Machines II, chapter 3
- Increase in starting torque with 1000 μF capacitor · Electric Machines II, chapter 3
- Capacitor for quadrature currents (4.5+j3.7 Ω) · Electric Machines II, chapter 3 · asked 2×
- Delta capacitor per phase for 50 kW motor · Basic Electrical Engineering, chapter 8
- Capacitor for single-phase motor pf correction · Basic Electrical Engineering, chapter 7
- Single-phase line capacitance, 6 mm, 1.3 m · Power System Analysis I, chapter 4
- DFRT and making single phase motor self-starting · Electrical Machines, chapter 7 · asked 3×