- 2072 Magh · 4 marks
Characteristic impedance, SIL, propagation constants
Short answer
Characteristic impedance Z_c = √(z/y) ≈ √(L/C) for lossless lines (~250–400 Ω). SIL = V_L²/Z_c, the load giving flat voltage. Attenuation constant α = Re(γ), phase shift constant β = Im(γ); α causes amplitude decay (neper/km), β causes phase shift (rad/km).
Define characteristic impedance, SIL, phase shift constant and attenuation constant for an overhead transmission line.
Let the line have series impedance and shunt admittance per unit length.
Characteristic (surge) impedance,
The ratio of voltage to current of a travelling wave on an infinitely long line (or a line terminated in ):
For a lossless line, , a pure resistance (about 400 Ω for single-conductor overhead lines, 250–300 Ω for bundled EHV lines, 40–60 Ω for cables). It does not depend on length.
Surge impedance loading (SIL)
The power delivered when the line feeds a resistive load equal to :
At SIL the reactive power generated by the line capacitance equals that absorbed by its inductance, so the voltage is flat along the line.
Propagation constant
per unit length.
Attenuation constant,
The real part of , in nepers per km. It shows how fast the magnitude of a voltage or current wave falls along the line (), because of losses in and . For a lossless line, .
Phase shift constant,
The imaginary part of , in radians per km. It shows how much the phase of the wave changes per unit length. For a lossless line:
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 200 mile line: Zc, propagation constant, SIL · Power System Analysis I, chapter 5
- 400 km line at UPF: Zc, propagation, regulation · Power System Analysis I, chapter 5
- Derive input impedance of transmission line · Electromagnetism, chapter 5
- 6° phase shift per 100 km of lossless line · High Voltage Engineering, chapter 3
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×