- 2071 Magh · 6 marks
200 mile line: Zc, propagation constant, SIL
Short answer
Characteristic impedance Zc = 406.4 angle -5.48° Ω; propagation constant gamma = 2.075×10⁻³ angle 84.52° per mile; attenuation constant alpha = 1.981×10⁻⁴ Np/mi; phase constant beta = 2.065×10⁻³ rad/mi; surge impedance loading SIL = 119.1 MW (using |Zc| from sqrt(z/y)).
A 200 mile long, 3-phase, 220 kV, 60 Hz overhead transmission line has series impedance of 0.8431∠79.04° Ω/mi and shunt admittance of 5.105 × 10⁻⁶∠90° S/mi. Determine the characteristic impedance, propagation constant, phase shift constant, attenuation constant and SIL of the line.
Given: mi, 220 kV, 60 Hz, /mi, S/mi.
Characteristic impedance
Propagation constant
For the whole line: .
Attenuation and phase-shift constants
Surge impedance loading
(Strictly, SIL is defined with the lossless surge impedance , which gives 120.2 MW. The difference is under 1%.)
Answer: , /mi, rad/mi, Np/mi, SIL MW (120.2 MW with the lossless ).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 280 km, 60 Hz line: nominal-π vs long line · Power System Analysis I, chapter 5 · asked 2×
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- 400 km line at UPF: Zc, propagation, regulation · Power System Analysis I, chapter 5
- 400 km long line, 60 MVA at 220 kV · Power System Analysis I, chapter 5
- Characteristic impedance, SIL, propagation constants · Power System Analysis I, chapter 5
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- Surge impedance and velocity of 220 kV line · High Voltage Engineering, chapter 3 · asked 2×
- Air clearances, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Conductor selection, 220 kV line for 200 MW · Transmission and Distribution System Design, chapter 4
- Peterson coil for 33 kV 60 km line · Switchgear and Protection, chapter 5 · asked 6×