Inductance of transposed double circuit, 0.9 cm radius

Short answer

For the double-circuit line, self GMD per phase Ds = ∛(Dsa Dsb Dsc) = 0.2362 m, with Dsa = √(r' Daa') etc. Mutual GMD between phases Dm = ∛(DAB DBC DCA) = 5.074 m. Inductance L = 2×10⁻⁷ ln(Dm/Ds) = 0.614 mH/km per phase.

A part of the transposition cycle of a 3-phase double circuit line is shown in figure. Radius of each conductor is 0.9 cm. The conductors are solid copper. Find the inductance per phase per km of the line. [Figure: vertical double-circuit arrangement; left column top to bottom a, b, c with 3 m vertical spacing between rows; right column top to bottom c', b', a'; horizontal distances a–c' = 6 m, b–b' = 7 m, c–a' = 6 m.]

For a transposed double-circuit line the inductance per phase is

L=2×10−7ln⁡DmDs H/mL = 2\times10^{-7}\ln\frac{D_m}{D_s}\ \text{H/m}

Here DmD_m is the equivalent mutual GMD between phase groups and DsD_s is the self-GMD of each phase (its two parallel conductors). Both are worked out for the section shown. By transposition, the other sections give the same result.

Geometry (section shown)

The tower is symmetrical, so the middle conductors b and b' each stand (7−6)/2=0.5(7-6)/2 = 0.5 m further out than the top and bottom conductors. Coordinates in metres, with c at the origin:

   a (0,6) ------- 6 m ------- c' (6,6)
    |3 m
 b (-0.5,3) ------ 7 m ------- b' (6.5,3)
    |3 m
   c (0,0) ------- 6 m ------- a' (6,0)
DistanceValue (m)
ab, bc, a'b', b'c'32+0.52=9.25=3.041\sqrt{3^2+0.5^2} = \sqrt{9.25} = 3.041
ab', a'b, bc', b'c32+6.52=51.25=7.159\sqrt{3^2+6.5^2} = \sqrt{51.25} = 7.159
ac, a'c', ac', a'c6, 6, 6, 6
aa', cc'72=8.485\sqrt{72} = 8.485
bb'7

Self-GMD

r′=0.7788×0.009=0.007009r' = 0.7788\times0.009 = 0.007009 m (solid copper).

Dsa=r′ Daa′=0.007009×8.485=0.2439 mDsb=r′ Dbb′=0.007009×7=0.2215 mDsc=r′ Dcc′=0.2439 mDs=0.2439×0.2215×0.24393=0.2362 m\begin{aligned} D_{sa} &= \sqrt{r'\,D_{aa'}} = \sqrt{0.007009\times8.485} = 0.2439\ \text{m}\\ D_{sb} &= \sqrt{r'\,D_{bb'}} = \sqrt{0.007009\times7} = 0.2215\ \text{m}\\ D_{sc} &= \sqrt{r'\,D_{cc'}} = 0.2439\ \text{m}\\ D_s &= \sqrt[3]{0.2439\times0.2215\times0.2439} = 0.2362\ \text{m} \end{aligned}

Mutual GMD

DAB=DabDab′Da′bDa′b′4=3.041×7.159×7.159×3.0414=4.666 mDBC=DbcDbc′Db′cDb′c′4=3.041×7.159×7.159×3.0414=4.666 mDCA=6×6×6×64=6 mDm=4.666×4.666×63=5.074 m\begin{aligned} D_{AB} &= \sqrt[4]{D_{ab}D_{ab'}D_{a'b}D_{a'b'}} = \sqrt[4]{3.041\times7.159\times7.159\times3.041} = 4.666\ \text{m}\\ D_{BC} &= \sqrt[4]{D_{bc}D_{bc'}D_{b'c}D_{b'c'}} = \sqrt[4]{3.041\times7.159\times7.159\times3.041} = 4.666\ \text{m}\\ D_{CA} &= \sqrt[4]{6\times6\times6\times6} = 6\ \text{m}\\ D_m &= \sqrt[3]{4.666\times4.666\times6} = 5.074\ \text{m} \end{aligned}

Inductance

L=2×10−7ln⁡5.0740.2362=2×10−7×3.0673=0.6135×10−6 H/m=0.6135 mH/km per phase\begin{aligned} L &= 2\times10^{-7}\ln\frac{5.074}{0.2362} = 2\times10^{-7}\times3.0673\\ &= 0.6135\times10^{-6}\ \text{H/m} = 0.6135\ \text{mH/km per phase} \end{aligned}

At 50 Hz this gives XL=314.16×0.6135×10−3=0.193 ΩX_L = 314.16\times0.6135\times10^{-3} = 0.193\ \Omega/km per phase.

Answer: Ds=0.236D_s = 0.236 m, Dm=5.074D_m = 5.074 m, and the inductance is 0.614 mH per phase per km.