- 2080 Chaitra · 10 marks
Inductance of transposed double circuit, 0.9 cm radius
Short answer
For the double-circuit line, self GMD per phase Ds = ∛(Dsa Dsb Dsc) = 0.2362 m, with Dsa = √(r' Daa') etc. Mutual GMD between phases Dm = ∛(DAB DBC DCA) = 5.074 m. Inductance L = 2×10⁻⁷ ln(Dm/Ds) = 0.614 mH/km per phase.
A part of the transposition cycle of a 3-phase double circuit line is shown in figure. Radius of each conductor is 0.9 cm. The conductors are solid copper. Find the inductance per phase per km of the line. [Figure: vertical double-circuit arrangement; left column top to bottom a, b, c with 3 m vertical spacing between rows; right column top to bottom c', b', a'; horizontal distances a–c' = 6 m, b–b' = 7 m, c–a' = 6 m.]
For a transposed double-circuit line the inductance per phase is
Here is the equivalent mutual GMD between phase groups and is the self-GMD of each phase (its two parallel conductors). Both are worked out for the section shown. By transposition, the other sections give the same result.
Geometry (section shown)
The tower is symmetrical, so the middle conductors b and b' each stand m further out than the top and bottom conductors. Coordinates in metres, with c at the origin:
a (0,6) ------- 6 m ------- c' (6,6)
|3 m
b (-0.5,3) ------ 7 m ------- b' (6.5,3)
|3 m
c (0,0) ------- 6 m ------- a' (6,0)
| Distance | Value (m) |
|---|---|
| ab, bc, a'b', b'c' | |
| ab', a'b, bc', b'c | |
| ac, a'c', ac', a'c | 6, 6, 6, 6 |
| aa', cc' | |
| bb' | 7 |
Self-GMD
m (solid copper).
Mutual GMD
Inductance
At 50 Hz this gives /km per phase.
Answer: m, m, and the inductance is 0.614 mH per phase per km.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- L and C of double circuit, 0.75 cm radius · Power System Analysis I, chapter 4
- Capacitance of double circuit line, 6 mm radius · Power System Analysis I, chapter 4
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4
- Capacitance of double circuit line, 9 mm radius · Power System Analysis I, chapter 4
- Transposition and inductance of transposed line · Power System Analysis I, chapter 4 · asked 2×
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- Conductor selection, 100 MW 80 km, no corona · Transmission and Distribution System Design, chapter 4
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4
- Tower dimensions for 220 kV double circuit line · Transmission and Distribution System Design, chapter 4 · asked 2×