- 2076 Bhadra · 8 marks
L and C of double circuit, 0.75 cm radius
Short answer
Compute equivalent mutual GMD and self GMD for each phase group using r' for inductance and r for capacitance. L = 0.622 mH/km per phase, C = 18.64 nF/km per phase to neutral.
A 3-Φ double circuit line is arranged as shown in figure below. The conductors are transposed. The radius of each conductor is 0.75 cm. Phase sequence is abc. Find the inductance and capacitance per phase per km. [Figure: vertical double-circuit arrangement; top row a and c' 4 m apart; middle row b and b' 5.5 m apart; bottom row c and a' 4 m apart; vertical spacing 3 m between rows.]
For a transposed double-circuit line, the two conductors of each phase act as a two-conductor group. We find the equivalent mutual GMD and the self-GMD of each phase group.
a o------ 4 m ------o c' --
3 m
b o------- 5.5 m -----o b' --
3 m
c o------ 4 m ------o a' --
Data: cm m, m. Horizontal offset of b from a is m.
Distances
| Pair | Distance (m) |
|---|---|
| ab, bc, a'b', b'c' | |
| ab', a'b, bc', b'c | |
| ac, a'c' | 6 |
| ac', a'c | 4 |
| aa', cc' | |
| bb' | 5.5 |
Mutual GMD
Inductance
Self GMD of each phase using :
Capacitance
Self GMD using actual radius :
Answer: mH/km per phase; nF/km (0.01864 µF/km) per phase to neutral.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Inductance of transposed double circuit, 0.9 cm radius · Power System Analysis I, chapter 4
- Capacitance of double circuit line, 6 mm radius · Power System Analysis I, chapter 4
- Inductance and capacitance of 4-conductor bundle line · Power System Analysis I, chapter 4
- Capacitance of double circuit line, 9 mm radius · Power System Analysis I, chapter 4
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4
- Inductance of 3-conductor bundled line, 6.1 m spacing · Power System Analysis I, chapter 4
- Capacitance matrices, untransposed and transposed (15 m) · High Voltage Engineering, chapter 5 · asked 3×
- Capacitance and charge matrices, transposed and untransposed · High Voltage Engineering, chapter 5
- Inductance of 420 kV line, transposed and untransposed · High Voltage Engineering, chapter 5
- Air clearances for 132 kV double circuit line · Transmission and Distribution System Design, chapter 4