Varley loop test for cable faults

Short answer

The Varley loop test links faulty and sound cores at the far end. With bridge ratio arms P and Q, first measure loop resistance RL = (Q/P)S1. Then with battery to earth, rebalance to get S2; fault distance from test end X = (P·RL – Q·S2)/(P+Q). When P=Q, X = (RL – S2)/2.

How can underground cable faults be located by the Varley loop test method? Explain with necessary figures and mathematical expressions.

The Varley loop test is a Wheatstone bridge method for locating earth faults and short-circuit faults in underground cables. It differs from the Murray loop in that the ratio arms PP and QQ are fixed, a variable resistor SS is adjusted for balance, and the loop resistance is measured in a separate step.

Connections

                battery + switch K
                       |
           P           B           Q
   A ----/\/\----------+---------/\/\---- C
   |                                      |
   +-----------------(G)------------------+
   |                                      |
   S (variable)                           |
   |                                      |
   D  <- K position 1                     |
   |                                      |
 faulty core (X to fault)          sound core (Y)
   |                                      |
   +======== link at far end =============+
   K position 2: earth (current enters through the fault)
  1. Link the faulty core and the sound core at the far end to form a loop.
  2. Connect the fixed ratio arms PP and QQ, with the variable resistor SS between A and the test end D of the faulty core. Connect the galvanometer across A and C.
  3. The battery is connected to the P–Q junction B. A two-way switch K connects its other terminal either to D, the test end of the loop (position 1), or to earth (position 2).

Step 1: loop resistance (K at position 1)

The bridge is an ordinary Wheatstone bridge, with SS in one arm and the whole loop RL=X+YR_L = X + Y in the other. Adjust SS to S1S_1 for balance:

PQ=S1RL  ⇒  RL=QPS1\frac{P}{Q} = \frac{S_1}{R_L} \;\Rightarrow\; R_L = \frac{Q}{P}S_1

Step 2: fault position (K at position 2, battery to earth)

The current now enters the loop through the fault. One arm is S+XS + X (variable resistor plus faulty core up to the fault), and the other arm is Y=RL−XY = R_L - X. Rebalance with S=S2S = S_2:

PQ=S2+XRL−X\frac{P}{Q} = \frac{S_2 + X}{R_L - X} PRL−PX=QS2+QX  ⇒  X=PRL−QS2P+QP R_L - P X = Q S_2 + Q X \;\Rightarrow\; X = \frac{P R_L - Q S_2}{P + Q}

With P=QP = Q (the usual case):

X=RL−S22X = \frac{R_L - S_2}{2}

Distance to the fault

If rr is the conductor resistance per metre:

x=Xrorx=XRL×2Lx = \frac{X}{r} \quad\text{or}\quad x = \frac{X}{R_L}\times 2L

where LL is the cable length (both cores of equal size).

Example

With P=QP = Q, RL=2 ΩR_L = 2\ \Omega for a 2 km cable (4 km of loop), and S2=0.6 ΩS_2 = 0.6\ \Omega:

X=(2−0.6)/2=0.7 Ω,x=0.7/2×4=1.4 kmX = (2 - 0.6)/2 = 0.7\ \Omega,\qquad x = 0.7/2\times 4 = 1.4\ \text{km}

The variable resistor allows finer balance than the Murray loop. The fault resistance is in the battery circuit, so it does not affect the result.