- 2070 Bhadra · 6 marks
Varley loop test for cable faults
Short answer
The Varley loop test links faulty and sound cores at the far end. With bridge ratio arms P and Q, first measure loop resistance RL = (Q/P)S1. Then with battery to earth, rebalance to get S2; fault distance from test end X = (P·RL – Q·S2)/(P+Q). When P=Q, X = (RL – S2)/2.
How can underground cable faults be located by the Varley loop test method? Explain with necessary figures and mathematical expressions.
The Varley loop test is a Wheatstone bridge method for locating earth faults and short-circuit faults in underground cables. It differs from the Murray loop in that the ratio arms and are fixed, a variable resistor is adjusted for balance, and the loop resistance is measured in a separate step.
Connections
battery + switch K
|
P B Q
A ----/\/\----------+---------/\/\---- C
| |
+-----------------(G)------------------+
| |
S (variable) |
| |
D <- K position 1 |
| |
faulty core (X to fault) sound core (Y)
| |
+======== link at far end =============+
K position 2: earth (current enters through the fault)
- Link the faulty core and the sound core at the far end to form a loop.
- Connect the fixed ratio arms and , with the variable resistor between A and the test end D of the faulty core. Connect the galvanometer across A and C.
- The battery is connected to the P–Q junction B. A two-way switch K connects its other terminal either to D, the test end of the loop (position 1), or to earth (position 2).
Step 1: loop resistance (K at position 1)
The bridge is an ordinary Wheatstone bridge, with in one arm and the whole loop in the other. Adjust to for balance:
Step 2: fault position (K at position 2, battery to earth)
The current now enters the loop through the fault. One arm is (variable resistor plus faulty core up to the fault), and the other arm is . Rebalance with :
With (the usual case):
Distance to the fault
If is the conductor resistance per metre:
where is the cable length (both cores of equal size).
Example
With , for a 2 km cable (4 km of loop), and :
The variable resistor allows finer balance than the Murray loop. The fault resistance is in the battery circuit, so it does not affect the result.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Murray loop test for cable faults · Power System Analysis I, chapter 2 · asked 5×
- Murray loop test for open and short circuit faults · Power System Analysis I, chapter 2 · asked 5×
- Cable fault location techniques and Murray loop · Power System Analysis I, chapter 2
- Locating faults in underground cables · Power System Analysis I, chapter 2 · asked 3×
- Underground cable laying systems · Industrial Power Distribution and Illumination, chapter 3
- Advantages of closed loop with mathematical support · Control Systems, chapter 1
- Subscriber loop and cable hierarchy · Telecommunications, chapter 1