Murray loop test for cable faults
Short answer
The Murray loop test locates a cable fault by forming a Wheatstone bridge with a sound core and the faulty core linked at the far end. At balance, fault distance from test end is x = [Q/(P+Q)] × 2l, where l is cable length. Fault resistance in the battery arm does not affect the result.
Explain Murray Loop test for locating short circuit fault in underground cable.
The Murray loop test is a bridge (Wheatstone principle) method to locate a short-circuit or earth fault in an underground cable. It needs one sound core running alongside the faulty core.
Connections
- At the far end, the faulty core and a sound core are joined by a low-resistance link, forming a loop.
- At the test end, the sound-core end (D) is connected to ratio arm and the faulty-core end (B) to ratio arm (both variable resistors); a galvanometer G is connected across D and B.
- A battery is connected between the junction A of and and earth (for an earth fault), or the other core in contact (for a short-circuit fault). The fault point completes the circuit.
A o-----[Battery]------+ Earth (sheath)
| :
+---+---+ : fault resistance
P Q :
| | :
D o--(G)--o B :
| | :
| +== faulty core =X========+
| <------ x -----> |
+========= sound core ============+
Test end Far end (cores joined)
Theory
The loop forms a Wheatstone bridge: , , (faulty core from test end to fault) and (sound core plus faulty core from far end back to fault). At balance (G reads zero):
is the total loop resistance (r per unit length). If both cores have the same cross-section, resistance is proportional to length:
where is the distance of the fault from the test end and the cable length.
Example
For a 500 m cable balanced at , : m from the test end.
Points to note
- Fault resistance appears in the battery arm, so it does not affect the balance (only sensitivity).
- Needs a sound core of known length; works best for low-resistance faults.
- If the cores differ in area, convert to equivalent lengths before using the formula.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Murray loop test for open and short circuit faults · Power System Analysis I, chapter 2 · asked 5×
- Cable fault location techniques and Murray loop · Power System Analysis I, chapter 2
- Varley loop test for cable faults · Power System Analysis I, chapter 2
- Locating faults in underground cables · Power System Analysis I, chapter 2 · asked 3×
- Locating phase-to-phase cable fault · Power System Analysis I, chapter 2