Murray loop test for open and short circuit faults

Short answer

For short-circuit faults, the Murray loop test uses a Wheatstone bridge with a sound core linked at the far end. Distance from test end is x = (Q/(P+Q)) * 2L. For open-circuit faults, capacitance comparison gives x = L * (Q/P) with P connected to the broken core.

Explain Murray Loop test for locating open and short circuit fault in underground cable.

The Murray loop test is a bridge method for locating faults in underground cables. For a short-circuit or earth fault it compares the resistance of the faulty core with the resistance of a sound core (Wheatstone bridge). For an open-circuit fault it compares capacitances.

Murray loop test (short-circuit or earth fault)

This is a Wheatstone bridge method. It needs one sound core running alongside the faulty core.

   +--------------(G)--------------+
   |                               |
   B ---/\/\------+------/\/\----- A
   |     P        |        Q       |
   |           battery             |
   |              |                |
   |            earth              |
 sound core                   faulty core
   |                               x  <- fault to earth
   |                               |
   +====== loop at far end ========+
  1. At the far end, connect the faulty core to the sound core with a low-resistance link, so the two cores form a loop.
  2. Connect ratio arm PP (a variable resistor) to the test end B of the sound core and ratio arm QQ to the test end A of the faulty core, and connect the galvanometer across A and B. Connect the battery between the junction of PP and QQ and earth (for an earth fault). For a short circuit between two cores, connect the battery to the other shorted core instead of earth.
  3. Adjust PP and QQ until the galvanometer reads zero.

Let RxR_x be the resistance of the faulty core from the test end to the fault, and RLR_L the resistance of the whole loop. The arm next to PP is the rest of the loop, RL−RxR_L - R_x, and the arm next to QQ is RxR_x. At balance:

PQ=RL−RxRx  ⇒  Rx=QP+Q RL\frac{P}{Q} = \frac{R_L - R_x}{R_x} \;\Rightarrow\; R_x = \frac{Q}{P+Q}\,R_L

If both cores have the same cross-section and the cable length is LL, resistance is proportional to length:

x=QP+Q×2Lx = \frac{Q}{P+Q}\times 2L

Here xx is the distance from the test end to the fault. The fault resistance carries only battery current, so it does not affect the balance.

Murray loop test for an open-circuit (broken-conductor) fault

A broken core gives no resistance loop, so capacitance is compared instead (the Murray capacitance loop). The capacitance of a core to the sheath is proportional to its length.

  1. At the far end, leave the broken core and the sound core open (insulated).
  2. Connect ratio arm PP to the broken core and ratio arm QQ to the sound core. Connect an AC source (or a battery with a key and a ballistic galvanometer) between the junction of PP and QQ and the sheath, and connect a detector between the two cores at the test end.
  3. Adjust PP and QQ for a null. The arm impedances are 1/ωCx1/\omega C_x (broken core up to the break, length xx) and 1/ωCL1/\omega C_L (sound core, full length LL). At balance:
PQ=1/ωCx1/ωCL=CLCx  ⇒  x=L CxCL=L QP\frac{P}{Q} = \frac{1/\omega C_x}{1/\omega C_L} = \frac{C_L}{C_x} \;\Rightarrow\; x = L\,\frac{C_x}{C_L} = L\,\frac{Q}{P}

(PP is the arm joined to the broken core.)

Points to note

  • The method needs at least one sound core of the same size.
  • It is accurate when the fault resistance is low enough for a sensitive galvanometer reading.
  • Fault-to-earth resistance does not affect the result, because it lies in the battery circuit.