- 2083 Baishakh (new course) · 5 marks
Two-conductor open circuit fault
Short answer
For a two-open-conductor fault (phases b and c open, phase a healthy), boundary conditions Ib=Ic=0 and Va=0 give equal sequence currents I0=I1=I2 and sequence voltages summing to zero. This forces the positive, negative and zero sequence networks between the break points to connect in series. The healthy-phase fault current is Ia=3E/(Z1+Z2+Z0).
Show that for the two-conductor open circuit fault in a 3-phase system, the sequence networks are to be connected in series to simulate the fault.
In a two-conductor open fault, two phases (say b and c) are broken between points and while phase a stays healthy. Writing the fault conditions in symmetrical components shows that the three sequence networks, seen between and , must be joined in series.
Fault conditions
p q
a --------------------------- (healthy, Ia flows)
b -----x x-------- (open, Ib = 0)
c -----x x-------- (open, Ic = 0)
Let be the series voltage drops across the break (from to ) in each phase.
- Phases b and c are open:
- Phase a is healthy (no break): (drop across the break in phase a is zero)
Sequence currents
so
The same current flows through all three sequence networks.
Sequence voltages
Since :
Sequence network equations
Seen from the break terminals -, each sequence network has a Thevenin form. Only the positive sequence network contains a source (the pre-fault open-circuit voltage or the equivalent driving voltage ):
Adding and using and :
Interpretation
Equal currents in all three networks and voltages that add to zero are exactly the conditions of three elements in series in a closed loop:
p1 +--[ +ve seq N/W, Z1, E ]--+ q1
| |
p2 +--[ -ve seq N/W, Z2 ]-----+ q2 (series loop:
| | q1->p2, q2->p0,
p0 +--[ zero seq N/W, Z0 ]----+ q0 q0->p1)
Hence the positive, negative and zero sequence networks are connected in series between the fault points to simulate a two-conductor open fault, and the healthy-phase current is . This is the series-fault counterpart of the single line-to-ground shunt fault.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- SLG fault: sequence networks in series · Power System Analysis II, chapter 5 · asked 5×
- Sequence networks decoupled for static circuit · Power System Analysis II, chapter 4
- Sequence networks with parallel transformer banks · Power System Analysis II, chapter 4
- DLG fault sequence network connection · Power System Analysis II, chapter 5 · asked 3×
- Sequence networks of Y load, neutral current · Power System Analysis II, chapter 4 · asked 2×
- L-G fault in phase B · Power System Analysis II, chapter 5
- Equivalent ABCD of two networks in series · Power System Analysis I, chapter 5
- Series connection of two-port networks · Filter Design, chapter 4
- Murray loop test for open and short circuit faults · Power System Analysis I, chapter 2 · asked 5×
- Fault level: two 40 MVA generators, 2 Ω feeder · Power Plant Equipment, chapter 4 · asked 5×