Effectiveness-NTU analysis of a heat exchanger

Short answer

Effectiveness ε = Q/Qmax; Qmax = Cmin(Th,in−Tc,in). NTU = UA/Cmin, Cr = Cmin/Cmax. The ε-NTU method is preferred when outlet temperatures are unknown. Cmin = 1680 W/K, Cr = 0.67, NTU = 0.625. ε = [1−exp(−0.625(0.33))]/[1−0.67exp(−0.625(0.33))] = 0.41. Q = 0.41×1680×115 = 79.2 kW. Th,out = 140−79160/1680 = 92.9°C, Tc,out = 25+79160/2508 = 56.6°C.

Explain the effectiveness-NTU method and state when it is preferred to the LMTD method. A counterflow heat exchanger has a surface area of 3 m^2 and U = 350 W/m^2 K. Hot oil (cp = 2100 J/kg K) at 0.8 kg/s enters at 140 °C and cold water (cp = 4180 J/kg K) at 0.6 kg/s enters at 25 °C. Find the effectiveness, the heat transfer rate and the outlet temperatures of both fluids. The counterflow effectiveness is e = [1 - exp(-NTU(1 - Cr))] / [1 - Cr exp(-NTU(1 - Cr))].

The effectiveness-NTU method

Effectiveness ε\varepsilon is the ratio of the actual heat transfer to the maximum possible:

ε=QQmax,Qmax=Cmin (Th,in−Tc,in)\varepsilon=\frac{Q}{Q_{max}},\qquad Q_{max}=C_{min}\,(T_{h,in}-T_{c,in})

where C=m˙cpC = \dot m c_p is the heat capacity rate. Number of transfer units NTU=UA/CminNTU = UA/C_{min} and capacity ratio Cr=Cmin/CmaxC_r = C_{min}/C_{max}. For each flow arrangement, ε=f(NTU,Cr)\varepsilon = f(NTU, C_r).

It is preferred when the outlet temperatures are unknown (rating or performance problems): the LMTD method would need trial and error, while the NTU method is direct. LMTD is easier for sizing when all four temperatures are known.

Solution

Heat capacity rates:

Ch=0.8×2100=1680 W/K,Cc=0.6×4180=2508 W/KC_h = 0.8\times2100 = 1680\ \text{W/K},\qquad C_c = 0.6\times4180 = 2508\ \text{W/K}

So Cmin=Ch=1680C_{min} = C_h = 1680 W/K (oil), Cmax=2508C_{max} = 2508 W/K.

Cr=16802508=0.670,NTU=UACmin=350×31680=0.625C_r = \frac{1680}{2508} = 0.670,\qquad NTU = \frac{UA}{C_{min}} = \frac{350\times3}{1680} = 0.625

Effectiveness (counterflow):

ε=1−e−0.625(1−0.670)1−0.670 e−0.625(1−0.670)=1−0.81341−0.5449=0.18660.4551=0.410\varepsilon = \frac{1-e^{-0.625(1-0.670)}}{1-0.670\,e^{-0.625(1-0.670)}} = \frac{1-0.8134}{1-0.5449} = \frac{0.1866}{0.4551}= 0.410

Heat transfer rate:

Q=εCmin(Th,in−Tc,in)=0.4097×1680×(140−25)=79 160 W≈79.2 kWQ = \varepsilon C_{min}(T_{h,in}-T_{c,in}) = 0.4097\times1680\times(140-25) = 79\,160\ \text{W}\approx79.2\ \text{kW}

Outlet temperatures:

Th,out=140−79 1601680=92.9 ∘C,Tc,out=25+79 1602508=56.6 ∘CT_{h,out} = 140 - \frac{79\,160}{1680} = 92.9\ ^\circ\text{C},\qquad T_{c,out} = 25 + \frac{79\,160}{2508} = 56.6\ ^\circ\text{C}

(For comparison, a parallel-flow exchanger of the same size would have ε=1−e−NTU(1+Cr)1+Cr=0.388\varepsilon = \frac{1-e^{-NTU(1+C_r)}}{1+C_r} = 0.388.)

Answer: ε≈0.41\varepsilon \approx 0.41; Q≈79.2Q \approx 79.2 kW; Th,out≈92.9T_{h,out} \approx 92.9 °C; Tc,out≈56.6T_{c,out} \approx 56.6 °C.