Short answer

Heat duty: Q = 2×2100×(100-60) = 168 kW. Water outlet: T_c2 = 20 + 168000/(1.2×4180) = 53.5°C. Counterflow LMTD: ΔT_lm = (46.5-40)/ln(46.5/40) = 43.2 K, A = 168000/(400×43.2) = 9.73 m². Parallel flow LMTD = (80-6.5)/ln(80/6.5) = 29.3 K, A = 168000/(400×29.3) = 14.3 m².

In a counterflow oil cooler, hot oil (cp = 2100 J/kg K) flows at 2 kg/s and is cooled from 100 °C to 60 °C by water (cp = 4180 J/kg K) flowing at 1.2 kg/s and entering at 20 °C. The overall heat transfer coefficient is 400 W/m^2 K. Determine (a) the heat duty, (b) the water outlet temperature, (c) the LMTD and the surface area required, and (d) the area if the exchanger were parallel flow with the same terminal temperatures.

(a) Heat duty

Q=m˙hch(Th1−Th2)=2×2100×(100−60)=168 000 W=168 kWQ = \dot m_hc_h(T_{h1}-T_{h2}) = 2\times2100\times(100-60) = 168\,000\ \text{W} = 168\ \text{kW}

(b) Water outlet

Tc2=Tc1+Qm˙ccc=20+168 0001.2×4180=20+33.49=53.5 ∘CT_{c2} = T_{c1}+\frac{Q}{\dot m_cc_c} = 20 + \frac{168\,000}{1.2\times4180} = 20 + 33.49 = 53.5\ ^\circ\text{C}

(c) Counterflow LMTD and area

 Oil   100 ----------> 60
 Water  53.5 <---------- 20

ΔT1=Th1−Tc2=100−53.5=46.5\Delta T_1 = T_{h1}-T_{c2} = 100 - 53.5 = 46.5 K, ΔT2=Th2−Tc1=60−20=40\Delta T_2 = T_{h2}-T_{c1} = 60 - 20 = 40 K.

ΔTlm=46.5−40ln⁡(46.5/40)=6.510.1505=43.2 K\Delta T_{lm} = \frac{46.5-40}{\ln(46.5/40)} = \frac{6.51}{0.1505} = 43.2\ \text{K} A=QU ΔTlm=168 000400×43.17=9.73 m2A = \frac{Q}{U\,\Delta T_{lm}} = \frac{168\,000}{400\times43.17} = 9.73\ \text{m}^2

(d) Parallel flow

Both fluids enter at the same end: ΔT1=100−20=80\Delta T_1 = 100 - 20 = 80 K, ΔT2=60−53.5=6.5\Delta T_2 = 60 - 53.5 = 6.5 K.

ΔTlm,p=80−6.5ln⁡(80/6.5)=73.52.510=29.3 K\Delta T_{lm,p} = \frac{80-6.5}{\ln(80/6.5)} = \frac{73.5}{2.510} = 29.3\ \text{K} Ap=168 000400×29.29=14.3 m2A_p = \frac{168\,000}{400\times29.29} = 14.3\ \text{m}^2

Parallel flow needs about 47 percent more area for the same duty, showing why counterflow is preferred.

Answer: Q=168Q = 168 kW; Tc2=53.5T_{c2} = 53.5 °C; ΔTlm=43.2\Delta T_{lm} = 43.2 K and A=9.73A = 9.73 m2^2 (counterflow); A=14.3A = 14.3 m2^2 (parallel flow).