Short answer

Using Dittus-Boelter correlation Nu = 0.023 Re^0.8 Pr^0.4 and log mean temperature difference: Re = 3.8e4, h = 4805 W/m^2K, heat gained Q = 40.7 kW, required tube length L = 2.2 m.

Water flows at a mean velocity of 1 m/s through a tube of inner diameter 25 mm and is heated from 30 °C to 50 °C. The tube wall is maintained at a uniform temperature of 90 °C. Evaluate water properties at the mean bulk temperature of 40 °C (rho = 992.2 kg/m^3, k = 0.631 W/m K, mu = 653 x 10^-6 Pa s, cp = 4179 J/kg K, Pr = 4.32). Using the Dittus-Boelter equation, calculate (a) the Reynolds number, (b) the heat transfer coefficient, (c) the heat gained by water per second, and (d) the length of the tube required.

(a) Reynolds number

Re=ρVDμ=992.2×1×0.025653×10−6=3.80×104Re = \frac{\rho V D}{\mu} = \frac{992.2\times1\times0.025}{653\times10^{-6}} = 3.80\times10^4

The flow is turbulent (Re>10 000Re > 10\,000) and the tube is long, so the Dittus-Boelter equation applies.

(b) Heat transfer coefficient

For heating of the fluid the exponent is n=0.4n = 0.4:

Nu=0.023 Re0.8Pr0.4=0.023 (37 986)0.8(4.32)0.4=190.4\begin{aligned} Nu &= 0.023\,Re^{0.8}Pr^{0.4}\\ &= 0.023\,(37\,986)^{0.8}(4.32)^{0.4} = 190.4 \end{aligned} h=Nu kD=190.4×0.6310.025=4805 W/m2Kh = \frac{Nu\,k}{D} = \frac{190.4\times0.631}{0.025} = 4805\ \text{W/m}^2\text{K}

(c) Heat gained

Mass flow rate:

m˙=ρVπD24=992.2×1×π(0.025)24=0.487 kg/s\dot m = \rho V\frac{\pi D^2}{4} = 992.2\times1\times\frac{\pi(0.025)^2}{4} = 0.487\ \text{kg/s} Q=m˙cp(Tout−Tin)=0.487×4179×20=40 700 WQ = \dot m c_p (T_{out}-T_{in}) = 0.487\times4179\times20 = 40\,700\ \text{W}

(d) Tube length

For constant wall temperature the mean temperature difference is the logarithmic mean:

ΔTlm=(90−30)−(90−50)ln⁡(90−3090−50)=60−40ln⁡1.5=49.3 ∘C\Delta T_{lm} = \frac{(90-30)-(90-50)}{\ln\left(\dfrac{90-30}{90-50}\right)} = \frac{60-40}{\ln1.5} = 49.3\ ^\circ\text{C} Q=h (πDL) ΔTlm  ⇒  L=40 7074805×π×0.025×49.3=2.19 mQ = h\,(\pi D L)\,\Delta T_{lm}\;\Rightarrow\; L = \frac{40\,707}{4805\times\pi\times0.025\times49.3} = 2.19\ \text{m}

Check: L/D=87.5>60L/D = 87.5 > 60, so the entrance effect is small and the correlation is acceptable.

Answer: Re=3.8×104Re = 3.8\times10^4; h=4805 W/m2h = 4805\ \text{W/m}^2K; Q=40.7Q = 40.7 kW; L≈2.2L \approx 2.2 m.