ADC with 8085 using 8255: fan and heater control

Short answer

8255 at 80H–83H, control word 91H: port A input (ADC data), port B output (PB0 heater, PB1 fan via optocouplers), PC4 START/ALE, PC5 OE, PC6 ADD A=1, PC0 EOC. ADC channel IN1 (001). Heater on for code <1AH (10°C), fan on for code >5AH (35°C).

You have to interface ADC with 8085 using 8255A ports. Interface a fan and a heater using opto couplers to derive the I/O devices. If the temperature is less than 10°C, turn on the heater and if the temperature is higher than 35°C, turn on the fan. Use port A of 8255 for transferring digital data output of ADC to the CPU and part C for control signals. Assume that an analog input is present at second input of the multiplexer and a clock input of suitable frequency is available for ADC. Also write an appropriate flow chart and algorithm to facilitate your design. Draw the diagram of your design.

Assumptions

8085 I/O mapped; 8255 at 80H (A), 81H (B), 82H (C), 83H (control). ADC0808 (8 channels, 8 bit), analog temperature signal at channel IN1 (ADD C B A = 001). Sensor LM35 (10 mV/deg C) with amplifier gain 5 so that 0-100 deg C = 0-5 V; 1 count = 0.39 deg C. Heater and fan are driven through opto-couplers (MOC3021 + triac or transistor + relay) from port B.

Threshold codes

10 deg C -> 10/100 x 255 = 25.5, take 1AH (26). 35 deg C -> 35/100 x 255 = 89.25, take 5AH (90).

Control word and port use

  • Port A: input (ADC data). Port B: output (PB0 = heater, PB1 = fan, via opto-couplers). Port C upper output: PC4 = START/ALE, PC5 = OE, PC6 = ADD A (high). Port C lower input: PC0 = EOC.
  • Control word: 1 00 1 0 0 0 1 = 1001 0001 = 91H.

Diagram

 LM35 -> amp -> IN1 --+
                      | ADC0808 -- D0-D7 --> PA0-PA7
 CLK (640 kHz) -------+  START,ALE <-- PC4
                         OE <------- PC5
                         ADD A <---- PC6 (=1), ADD B, C = GND
                         EOC ------> PC0
 8085 <-> 8255 (AD0-7, IOR', IOW', A0, A1, CS')
 PB0 -> [Opto-coupler] -> Heater driver -> Heater
 PB1 -> [Opto-coupler] -> Fan driver -> Fan

Algorithm

  1. Initialise the 8255 (91H); turn heater and fan off.
  2. Select channel 1, give START/ALE pulse.
  3. Wait for EOC = 1.
  4. Enable OE, read port A (temperature code), disable OE.
  5. If code < 1AH: heater ON, fan OFF.
  6. Else if code > 5AH: fan ON, heater OFF.
  7. Else both OFF.
  8. Repeat from step 2.
 START -> Init -> Start conversion -> EOC? -no-> wait
   -> Read data -> T < 10 ? -yes-> Heater ON
                        -no-> T > 35 ? -yes-> Fan ON
                                       -no-> both OFF
   -> back to Start conversion

Program

        MVI A,91H
        OUT 83H
        MVI A,00H
        OUT 81H          ; heater, fan off
LOOP:   MVI A,40H        ; ADD A=1, START=0
        OUT 82H
        MVI A,50H        ; START/ALE = 1
        OUT 82H
        MVI A,40H        ; START = 0 : conversion begins
        OUT 82H
WAIT:   IN 82H
        ANI 01H          ; EOC (PC0)
        JZ WAIT
        MVI A,60H        ; OE = 1
        OUT 82H
        IN 80H           ; read temperature
        MOV B,A
        MVI A,40H        ; OE = 0
        OUT 82H
        MOV A,B
        CPI 1AH
        JC HEAT          ; below 10 C
        CPI 5BH
        JNC FAN          ; above 35 C
        MVI A,00H        ; between: both off
        OUT 81H
        JMP LOOP
HEAT:   MVI A,01H
        OUT 81H
        JMP LOOP
FAN:    MVI A,02H
        OUT 81H
        JMP LOOP

✓ Answer checked by Claude Sonnet 5.5

All Instrumentation II chapter 4 questions →