Bus classification in load flow

Short answer

Slack bus: specified |V| and δ, found P and Q. PV bus: specified P and |V|, found Q and δ (with Q limits). PQ bus: specified P and Q, found |V| and δ. In N-R load flow, unknowns are δ at N−1 non-slack buses and |V| at N−1−m PQ buses.

Classify and distinguish different buses used in load flow (Newton-Raphson) analysis. Mention the specified quantities and the variables to be obtained from load flow for each bus type.

In load-flow analysis each bus ii has four quantities: real power PiP_i, reactive power QiQ_i, voltage magnitude ∣Vi∣|V_i| and voltage angle δi\delta_i. Two are specified and the other two are found by the load flow. On this basis buses are of three types.

1. Slack (swing / reference) bus

  • Usually the largest generating station; only one in the system.
  • Specified: ∣V∣|V| and δ\delta (normally δ=0∘\delta = 0^\circ, the reference angle).
  • Found: PP and QQ.
  • Its generation supplies the difference between total load plus the (initially unknown) losses and the scheduled generation of other units.

2. PV (generator / voltage-controlled) bus

  • Buses with generators, synchronous condensers or SVCs that can hold voltage.
  • Specified: PP (set by turbine) and ∣V∣|V| (set by AVR); limits QminQ_{min}, QmaxQ_{max}.
  • Found: QQ and δ\delta.
  • If computed Q goes outside its limits, Q is fixed at the limit and the bus becomes a PQ bus.

3. PQ (load) bus

  • Buses with only loads (or fixed generation); about 80–90% of all buses.
  • Specified: PP and QQ (net injection PG−PDP_G - P_D, QG−QDQ_G - Q_D).
  • Found: ∣V∣|V| and δ\delta.

Summary

Bus typeSpecifiedTo be foundNumber
Slack∣V∣\lvert V\rvert, δ\deltaP, Q1
PVP, ∣V∣\lvert V\rvertQ, δ\deltam
PQP, Q∣V∣\lvert V\rvert, δ\deltaN − m − 1

In N-R analysis this gives (N−1)(N-1) P-equations (all except slack) and (N−1−m)(N-1-m) Q-equations (PQ buses only).

✓ Answer checked by Claude Sonnet 5.5