Short answer

The slack bus absorbs the system losses unknown before solution, sets the phase angle reference (usually 0°), and ensures the number of equations equals unknowns by leaving its P and Q free. It is normally the largest generator, and its power is computed last from the converged voltages.

What is the significance of slack bus in load flow analysis?

The slack (swing) bus is the bus where the voltage magnitude and angle are specified (usually 1.0∠0∘1.0\angle 0^\circ pu or a set value) and the real and reactive power are unknown.

Its significance:

  • Supplies the unknown losses. Line losses are not known until the load flow is solved, so one generator must supply the difference between total generation and total load plus losses.
  • Phase angle reference. Its angle is taken as 0∘0^\circ and all other bus angles are measured from it.
  • Makes the equations solvable. It leaves two known and two unknown quantities at every bus.
  • It is normally the largest generating station in the system. Its PP and QQ are found at the end from P1−jQ1=V1∗∑kY1kVkP_1 - jQ_1 = V_1^{*}\sum_k Y_{1k}V_k.