Design wind pressure, large openings, 100 yr

Short answer

Design wind pressure is 2.17 kN/m², corresponding to a design wind speed of 60.2 m/s.

A building with large openings of size over 50 m and height 15 m is planned in a city to have a 100 years life. The building is planned to be located on a downward slope of 160 m high hill, the slope of which is 1 vertical and 3 horizontal. The building has to be constructed at a height of 100 m above the base of hill. The terrain is an open terrain with scattered obstruction, the heights of obstructions being in the range of 1.5 m to 10 m above the ground level. Determine the design wind pressure.

Assumptions (not all data are given). Basic wind speed is not stated, so Vb=47V_b = 47 m/s is assumed. Building: dimension over 50 m, so Class C; height 15 m. Terrain: open with scattered obstructions 1.5 to 10 m high, so Category 2. Design life 100 years. Large openings (more than 20% of wall area).

Step 1: Design wind speed

  • k1k_1: for a life of 100 years and Vb=47V_b = 47 m/s, Table 1 gives k1=1.07k_1 = 1.07.
  • k2k_2: Category 2, Class C, at 15 m: interpolating between 10 m (0.93) and 15 m (0.97): k2=0.970k_2 = 0.970, i.e. 0.970.97 (Table 2).
  • k3k_3 (Appendix C): hill height Z=160Z = 160 m, slope 1 vertical to 3 horizontal, θ=tan⁡−1(1/3)=18.4∘>17∘\theta = \tan^{-1}(1/3) = 18.4^\circ > 17^\circ, so C=0.36C = 0.36 and Le=Z/0.3=533L_e = Z/0.3 = 533 m. The building is on the downward (leeward) slope at 100 m above the base, i.e. 60 m below the crest, so the horizontal distance from the crest is X=60×3=180X = 60\times3 = 180 m downwind: X/Le=0.337X/L_e = 0.337; H/Le=15/533=0.028H/L_e = 15/533 = 0.028. From Fig. 15, s≈0.65s \approx 0.65 (read from the chart; approximate). k3=1+Cs=1+0.36×0.65=1.234k_3 = 1 + Cs = 1 + 0.36\times0.65 = 1.234 (within the limit 1.36).
Vz=Vbk1k2k3=47×1.07×0.97×1.234=60.2 m/spz=0.6Vz2=0.6×60.22=2174 N/m2=2.17 kN/m2\begin{aligned} V_z &= V_bk_1k_2k_3 = 47\times1.07\times0.97\times1.234 = 60.2\ \text{m/s} \\ p_z &= 0.6V_z^2 = 0.6\times60.2^2 = 2174\ \text{N/m}^2 = 2.17\ \text{kN/m}^2 \end{aligned}

Step 2: Net pressure with large openings

For openings above 20% of the wall area, Cpi=±0.7C_{pi} = \pm0.7 (cl. 6.2.3.2). Taking the external coefficients of a rectangular clad building (Table 4, h/w<1/2h/w < 1/2, wind 0°): windward wall Cpe=+0.7C_{pe} = +0.7, leeward wall −0.5-0.5.

SurfaceCpeC_{pe}Cpe−CpiC_{pe} - C_{pi} with Cpi=−0.7C_{pi} = -0.7with Cpi=+0.7C_{pi} = +0.7
Windward wall+0.7+1.4 (3.04 kN/m²)0.0
Leeward wall-0.5+0.2 (0.43 kN/m²)-1.2 (-2.61 kN/m²)

Answer

Design wind speed Vz=60.2V_z = 60.2 m/s; design wind pressure pz≈2174p_z \approx 2174 N/m² (≈2.17\approx 2.17 kN/m²). The largest net pressure on the walls is 1.4pz≈3.041.4p_z \approx 3.04 kN/m² (inward on the windward wall with the internal suction case) and the largest net suction is 1.2pz≈2.611.2p_z \approx 2.61 kN/m².

All Design of Steel and Timber Structure chapter 8 questions →