Controller design with 8 samples per cycle, step response and Kv
Short answer
Digital controller: GD(z)=0.7991(z-0.3679)/(z-0.1926). The step response overshoots by 16.3% and settles to 1. Static velocity error constant Kv=0.626 s^-1.
Consider a digital control system shown in figure below. The plant is a second order system described as G(s)=1/s(s+1). The sampling period of the system is taken to be T = 1 s. Design a digital controller such that the dominant closed loop poles of the system will have damping ratio ζ=0.5 and number of samples per cycle of damped sinusoidal oscillation to be 8. Following the design, obtain the unit step response of the designed system and static velocity error constant Kᵥ. [Figure: unity-feedback loop: R(s) → summing junction → sampler (T = 1 s) → digital controller → ZOH → G(s) → Y(s)]
Step 1: Plant pulse transfer function ( s)
Step 2: Desired poles
With 8 samples per cycle, , and
Step 3: Angle condition
| Factor | Angle at |
|---|---|
| zero at | |
| pole at | |
| pole at | |
| Total |
The controller must add , so a lead compensator is needed.
Step 4: Lead controller
The zero cancels the plant pole at 0.3679 and adds . The controller pole must contribute :
Step 5: Gain
Step 6: Closed-loop pulse transfer function
The poles are , as desired. ✔
Step 7: Unit step response
With , the difference equation is , where :
| 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 0 | 0.294 | 0.769 | 1.078 | 1.163 | 1.115 | 1.038 | 0.987 | 0.973 | 0.981 | 0.994 |
The maximum overshoot is about 16.3% at , which matches . One damped cycle takes about 8 samples, and (type-1 system).
Step 8: Static velocity error constant
Answer: . The step response overshoots by 16.3% and settles to 1, and .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Digital PI design, plant e^(−5s)/(s+0.4), step response · Digital Control System, chapter 4
- Root-locus design: 8 samples per cycle, T = 0.2 s · Digital Control System, chapter 4
- Digital PI design, plant e^(−5s)/(s+0.4), Kv · Digital Control System, chapter 4 · asked 2×
- Digital PD controller design for plant 1/s² · Digital Control System, chapter 4 · asked 2×
- Digital PI design for plant with 2 s dead time · Digital Control System, chapter 4 · asked 3×
- Controller design for peak time 1.2 s (ζ = 0.55), Kv · Digital Control System, chapter 4 · asked 2×
- Second order model from step response (peak 1.25) · Control Systems, chapter 3
- Second-order step response and damping · Instrumentation and Measurement, chapter 4
- First-order system impulse and step response · Signals and Systems, chapter 5
- Second-order transducer frequency and step response · Instrumentation and Measurement, chapter 4