MCB, MCCB and HRC fuse comparison

Short answer

MCB trips via thermal bimetal for overload and magnetic solenoid for short circuit. MCB rated ≤125A, breaking capacity 6-25kA, fixed; MCCB rated up to 2500A, breaking 16-200kA, adjustable. HRC fuse melts, very fast, breaking 80-200kA, must replace; MCCB is reusable, adjustable, can switch. Rupturing capacity: MCB 6-25kA, MCCB 16-200kA, HRC 80-200kA.

Explain the operating principle of MCB. What are the difference between MCB and MCCB? Compare HRC fuse with MCCB. What is rupturing capacity of MCB, MCCB and HRC fuse?

Operating principle of MCB

An MCB has a thermal and a magnetic trip acting on a common latch:

  • Thermal (overload): load current heats a bimetal strip; on sustained overload it bends and trips the latch after an inverse-time delay.
  • Magnetic (short circuit): a solenoid in series pulls its plunger instantly when current exceeds a set multiple of rated current (B: 3–5 × In, C: 5–10 × In, D: 10–20 × In), tripping the latch and helping to open the contacts.
  • The arc is drawn into an arc chute of metal plates, split and cooled until it goes out. The MCB is then reset by its lever.

MCB vs MCCB

PointMCBMCCB
Current ratingUp to about 100–125 AAbout 16 A to 2500 A
Breaking capacity6–10 kA (max about 25 kA)16–200 kA
Trip settingFixedAdjustable (thermal and magnetic)
Trip unitThermal-magneticThermal-magnetic or electronic
Poles1, 2, 3, 4 (DIN rail)3 or 4, bolted
ExtrasFewShunt trip, under-voltage, aux contacts, motor operator
UseFinal circuits in buildingsFeeders, motors, main incomers

HRC fuse vs MCCB

PointHRC fuseMCCB
PrincipleMelting of silver element in quartz sandThermal-magnetic/electronic trip with contacts
After faultMust be replacedReset and reused
SpeedVery fast; current limitingSlower (unless current-limiting type)
Breaking capacity80–120 kA (up to 200 kA)16–200 kA
AdjustabilityNoneAdjustable settings
Switching dutyCannot switch loadCan switch load on/off
Single phasingOne fuse may blow, motor single-phasesAll poles open together
CostLowHigh
Remote operationNot possiblePossible (shunt trip)

Rupturing (breaking) capacity

The rupturing capacity is the maximum prospective short-circuit current a device can interrupt safely at rated voltage. Typical values:

  • MCB: 6 kA or 10 kA (IEC 60898), up to about 25 kA.
  • MCCB: 16 kA to about 100 kA, some up to 200 kA (IEC 60947-2).
  • HRC fuse: 80 kA to 120 kA, some up to 200 kA.

The device's breaking capacity must be higher than the fault level at the point where it is installed.