Short answer

Fuse melts irreversibly; MCB uses thermal (bimetal) and magnetic trips, is resettable and usable as a switch. HRC fuse cut-off current is the maximum instantaneous current reached before element melts, limiting peak fault current. Pre-arcing time is the interval from fault inception to element melting. Arcing time is the duration from arc initiation to final extinction; total clearing time is their sum.

What is the main difference between Fuse and MCB? Define the following terms for HRC fuse: (i) cut off (ii) pre-arcing time (iii) arcing time.

Difference between fuse and MCB

PointFuseMCB (miniature circuit breaker)
Operating principleFuse element melts by I²R heatingThermal (bimetal) trip for overload + magnetic trip for short circuit
ReuseOne-time; element must be replacedReset and reused after tripping
Speed on short circuitVery fast; HRC fuse cuts off before first peakFast (magnetic, ~5–10 ms), but slower than HRC
Breaking capacityVery high (HRC up to 80–120 kA)Limited (typically 6–10 kA)
SwitchingCannot be used as a switchCan be used as an ON/OFF switch
IndicationNot always visibleHandle position shows tripped state
CostLow initial costHigher initial, but no replacement cost
Single phasingPossible when one fuse blowsMulti-pole MCB trips all poles

HRC fuse terms

(i) Cut-off (cut-off current): the maximum instantaneous value of current actually reached before the fuse element melts, when the prospective fault current is large. An HRC fuse melts before the first peak of the fault current, so the cut-off current is much lower than the prospective peak; this limits thermal and electromagnetic stress on the circuit.

(ii) Pre-arcing time (melting time): the time from the start of the fault current until the fuse element melts and an arc is initiated. It depends on the magnitude of current; for heavy faults it is a few milliseconds.

(iii) Arcing time: the time from the instant the arc is initiated (element melts) until the arc is finally extinguished and the current becomes zero. Silica sand absorbs the arc energy and quenches the arc.

 i   prospective
 │     ╱‾╲
 │ cut-off ●╲   actual current
 │    ╱│   ╲
 │   ╱ │    ╲___
 └──┴──┴──────┴────► t
    pre-arc  arcing
   ◄──────►◄────►
   total operating time

Total operating (clearing) time = pre-arcing time + arcing time.