Quartz sand absorbs arc energy, forms high-resistance fulgurite, extinguishing the arc silently. Cut-off current is the peak reached before melting, much lower than prospective; total operating time <5 ms. HRC fuses have very high breaking capacity, current limitation, reliable tripping, no deterioration, and are tamper-proof; Kit-Kat fuses have low breaking capacity, uncertain operation, and risk of rewiring with wrong wire.

Why the HRC fuses are surrounded by quartz sand? Explain cut-off current characteristics of HRC fuse and state the advantages of HRC fuse over Kit-Kat fuse.

An HRC (high rupturing capacity) fuse is a cartridge fuse that can safely interrupt very large fault currents (up to 80–100 kA or more) because its element is enclosed in a ceramic body filled with quartz sand.

Why HRC fuses are filled with quartz sand

  • When the silver element melts, it vaporises and an arc forms. The silver vapour reacts with the quartz (silica) sand and forms a high-resistance glass-like substance (fulgurite).
  • The sand absorbs the arc heat, cools and de-ionises the arc path, and quickly raises the arc resistance, so the arc is extinguished within a few milliseconds.
  • The sand also stops the arc and hot metal vapour from bursting out of the cartridge, so the operation is silent, without flame or explosion.
  • Because the arc is quenched before the current reaches its prospective peak, the fuse limits the fault current.

Cut-off characteristics of HRC fuse

 i
 |        prospective current (no fuse)
 |       .-'''-.
 |     .'       '.
 |    /  Ic       \
 |   /  /\ cut-off  \
 |  /  /  \          \
 | /  /    \          \
 |/__/______\__________\___ t
   tp  ta
 tp = pre-arcing time, ta = arcing time
 total operating time = tp + ta
  • Prospective current: the current that would flow if the fuse were replaced by a link of negligible impedance.
  • Cut-off current (Ic): the maximum instantaneous current actually reached before the fuse element melts. For large faults the HRC fuse melts in the first quarter cycle, so Ic is much smaller than the prospective peak.
  • Pre-arcing time: from fault start to element melting. Arcing time: from melting to final arc extinction. Their sum is the total operating time (often < 5 ms for heavy faults).
  • Cut-off current rises with the prospective current but much more slowly; manufacturers give cut-off charts (Ic vs prospective current) for each fuse rating. This reduces I²t and the electromagnetic and thermal stress on cables, busbars and switchgear.

Advantages of HRC fuse over Kit-Kat (rewirable) fuse

HRC fuseKit-Kat (rewirable) fuse
Breaking capacity very high (tens of kA)Low breaking capacity (a few kA)
Current-limiting, cuts off before peakNot current-limiting
Fast and accurate operation, reliable inverse-time curveOperation uncertain; depends on wire used
No deterioration with age, no external arcElement oxidises; may flash when blowing
Cannot be wrongly rewired with thicker wireCan be rewired with wrong size wire
Good discrimination with other fuses and breakersPoor discrimination
Sealed; safe for operatorOpen element; risk of fire

Kit-Kat fuses are cheaper and easy to renew, but HRC fuses are preferred for motor circuits, transformers and main feeders in industry.