- 2075 Baisakh · 6 marks
HRC fuse I²t and fuses in series
Short answer
HRC fuse time-current curve is inverse; for short times (<10 ms) melting depends on I²t energy. Pre-arcing I²t is constant at high currents. For series fuses, the downstream fuse's total let-through I²t must be less than the upstream fuse's pre-arcing I²t to prevent upstream melting, and time-current curves must not cross.
Describe the time/current I²t characteristics of a HRC fuse and explain how they are used to select the ratings of fuses in series.
Time–current and I²t characteristics of an HRC fuse
The time–current characteristic shows the operating time against current on log–log scales. It is inverse: long times for small overloads, a few milliseconds for heavy faults.
For short operating times (less than about 10 ms) heat cannot escape from the element, so melting depends only on the energy I²t delivered:
Pre-arcing I²t = ∫₀^tp i² dt (energy to melt element)
Arcing I²t = ∫tp^tt i² dt (energy during arc)
Total I²t = pre-arcing I²t + arcing I²t
I²t (A²s, log)
│ total I²t ─────────────
│ ╱ (rises with voltage; higher at low pf)
│ pre-arcing I²t ────────
│ (constant at high current)
└─────────────────────────► prospective I
- Pre-arcing I²t is practically constant for a given fuse at high currents (fixed by element mass and material).
- Total (let-through) I²t depends on circuit voltage, power factor and prospective current.
- Manufacturers give both values for each rating.
Selection of fuses in series using I²t
For a minor (downstream) fuse F2 and a major (upstream) fuse F1:
Supply ──[F1]──┬──[F2]── load
fault after F2
- Both fuses carry the same fault current.
- For F1 not to blow or be damaged, the energy let through by F2 in clearing the fault must not melt F1:
Total I²t of F2 < Pre-arcing I²t of F1
- At lower currents (long times) the time–current curves must not cross; the major fuse curve must lie above the minor fuse curve with a margin.
- Choose F2 from the load current; then choose the smallest F1 that satisfies the I²t rule. In practice a rating ratio of about 1.6–2 : 1 is sufficient for gG fuses.
Example (illustrative values): a 63 A fuse with total I²t ≈ 15 000 A²s and a 125 A fuse with pre-arcing I²t ≈ 30 000 A²s discriminate, since 15 000 < 30 000.
The total I²t of the fuse must also be less than the withstand I²t (k²S²) of the protected cable or semiconductor, so the I²t data also fix the maximum fuse rating for a given cable.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Cut-off and time-current characteristics of fuse · Switchgear and Protection, chapter 3
- HRC fuse operating characteristics and applications · Switchgear and Protection, chapter 3
- Fuse vs MCB; HRC fuse time terms · Switchgear and Protection, chapter 3
- Fuse time-current factors and coordination · Switchgear and Protection, chapter 3
- Prospective current, cut-off current, time delay fuse · Switchgear and Protection, chapter 3
- Fuse and contactor ratings for induction motor · Switchgear and Protection, chapter 3
- Cut-off current characteristics of HRC fuse · Industrial Power Distribution and Illumination, chapter 3
- HRC fuse quartz sand, cut-off, vs Kit-Kat · Industrial Power Distribution and Illumination, chapter 3
- Types of fuse, phase wire, HRC use · Industrial Power Distribution and Illumination, chapter 3
- Fuse vs MCB and HRC rupturing capacity · Industrial Power Distribution and Illumination, chapter 3 · asked 3×