Short answer

Fuse melts and needs replacement; MCB trips on overload/short circuit via bimetal and solenoid, and resets. MCB's thermal trip bends bimetal, magnetic trip pulls plunger. HRC fuse rupturing capacity (80-120 kA) is its safe interruption limit, using quartz sand to quench arc and limit cut-off current.

What are the difference between Fuse and MCB? Explain the operating principle of MCB. Discuss about rupturing capacity of HRC fuse.

Difference between fuse and MCB

PointFuseMCB
PrincipleFuse wire melts by I²R heatThermal bimetal + magnetic trip
After operationMust be replaced/rewiredSimply reset by the lever
Speed on short circuitVery fast (current limiting)Fast (magnetic trip, 2–10 ms)
Overload protectionPoor, not exactAccurate, inverse-time
SwitchingCannot be used as switchAlso works as an ON/OFF switch
IndicationNot clear which fuse blewLever shows tripped state
TamperingCan be wrongly rewiredCannot be tampered easily
CostLowHigher

Operating principle of MCB

An MCB (miniature circuit breaker) has two trip elements acting on one latch mechanism:

 Line ─┬─[contacts]──[bimetal]──[coil]── Load
       │      ▲          │         │
       │      └── latch ─┴─────────┘
       └ arc chute (splits the arc)
  1. Thermal trip (overload): the load current passes through a bimetal strip. On a sustained overload the strip heats, bends and releases the latch. The time delay is inversely related to the current, so small overloads take longer to trip.
  2. Magnetic trip (short circuit): a solenoid coil carries the current. A large short-circuit current (for example 3–5 × In for B curve, 5–10 × In for C curve, 10–20 × In for D curve) pulls the plunger instantly, which trips the latch and also pushes the moving contact open.
  3. Arc quenching: the arc formed between opening contacts is driven into an arc chute of steel plates, where it is split, cooled and extinguished.

Rupturing capacity of HRC fuse

The rupturing (breaking) capacity of a fuse is the largest prospective fault current (r.m.s.) that it can safely interrupt at rated voltage without damage or danger. It is expressed in kA (or MVA).

  • HRC (high rupturing capacity) fuses have a silver element inside a ceramic body filled with pure quartz sand. When the element melts, the sand absorbs the arc energy and forms a high-resistance glass-like substance (fulgurite), which quenches the arc quickly.
  • Because the fuse melts before the fault current reaches its peak, it limits the cut-off current, so the actual current is much lower than the prospective current.
  • Typical breaking capacity of LV HRC fuses is 80 kA to 120 kA (some up to 200 kA), far higher than MCBs (6–10 kA) and comparable to large MCCBs.
  • This makes HRC fuses suitable near transformers and in main panels where fault levels are very high, and as back-up protection for MCBs.