- 2080 Chaitra · 10 marks
Office lighting design with CFL luminaires
Short answer
32 CFL luminaires of 30 W each (3600 lm) in an 8×4 grid, spacing 2.5 m. Total lighting load 960 W, achieving 250.4 lux with UF=0.69, MF=0.63, and 120 lm/W efficacy.
An office has length of 20m, width of 10m and height of 3m. The ceiling to desk height is 2m and the area to be illuminated to a general is 250 lux using CFL Luminaire with a SHR(max) of 1.25. The maintenance factor is 0.63, Utilization factor is 0.69 and Efficiency of Lamp is 120lumen/Watt. Design a lighting system for this office with number of Lamps, sizing of lamps, luminaries layout, wiring layout and distribution system layout.
Given: room 20 m × 10 m × 3 m, mounting height above desk Hm = 2 m, E = 250 lux, SHR(max) = 1.25, MF = 0.63, UF = 0.69, lamp efficacy 120 lm/W. Assumptions: ceiling-mounted CFL/LED-type luminaires, pf 0.9; 6 power sockets (16 A, 1 kW each) for office equipment; 3-phase, 400/230 V, 4-wire supply.
Number and size of lamps
The number is fixed by the maximum spacing (for uniformity), then the lamp size is fixed by the lumens needed.
Max spacing S = SHR × Hm = 1.25 × 2 = 2.5 m
Along length: 20/2.5 = 8 rows; along width: 10/2.5 = 4
Number of luminaires N = 8 × 4 = 32
Total lumens = E × A / (UF × MF)
= 250 × 200 / (0.69 × 0.63) = 115022 lm
Lumens per luminaire = 115022 / 32 = 3594.4 lm
Lamp wattage = 3594.4 / 120 = 29.95 W → choose 30 W lamp
Lumens per 30 W lamp = 30 × 120 = 3600 lm
Answer: 32 luminaires of 30 W each (3600 lm), in 8 × 4 grid, total lighting load 960 W.
Arrangement and spacing
Spacing along length = 20/8 = 2.5 m
Spacing along width = 10/4 = 2.5 m
End spacing (to wall) = half of these
Max spacing = SHR × Hm = 1.25 × 2 = 2.5 m
2.5 m and 2.5 m ≤ 2.5 m → OK
Actual E = 32 × 3600 × 0.69 × 0.63 / 200
= 250.4 lux (≥ 250 lux required)
Layout diagram
Plan 20 m × 10 m (letter = phase of lamp circuit)
+-----------------+
| R R R R R R Y Y |
| B B B B Y Y Y Y |
| B B B B B B R R |
| Y Y Y Y Y R R R |
+-----------------+
[DB] [SB] <- entrance: DB and switch board
S S S S ... one switch per sub-circuit
Each light sub-circuit is controlled by one 6 A one-way switch; all switches are grouped on a switch board (SB) next to the entrance, and the DB is mounted beside it. Power sockets (16 A, 3-pin, with earth) are placed along the walls at about 1 m height, spaced roughly evenly.
Sub-circuits
Rule (IS 732 / NEA practice): a light sub-circuit carries at most 10 points and 800 W. Here one luminaire is 30 W, so up to 10 luminaires per sub-circuit. Number of circuits is made a multiple of 3 for phase balance.
| Circuit | Luminaires | Load (W) | Current (A) | Phase | MCB |
|---|---|---|---|---|---|
| L1 | 6 | 180 | 0.87 | R | 6 A |
| L2 | 6 | 180 | 0.87 | Y | 6 A |
| L3 | 5 | 150 | 0.72 | B | 6 A |
| L4 | 5 | 150 | 0.72 | B | 6 A |
| L5 | 5 | 150 | 0.72 | R | 6 A |
| L6 | 5 | 150 | 0.72 | Y | 6 A |
Power sub-circuits (assumed): 6 sockets of 16 A, each taken as 1 kW, at most 2 sockets per power sub-circuit (IS 732), 2.5 mm² Cu wire, 20 A MCB.
| Circuit | Sockets | Load (W) | Phase | MCB |
|---|---|---|---|---|
| P1 | 2 | 2000 | R | 20 A |
| P2 | 2 | 2000 | Y | 20 A |
| P3 | 2 | 2000 | B | 20 A |
Distribution board design
| Phase | Circuits | Load (W) | Current (A) |
|---|---|---|---|
| R | L1, L5, P1 | 2330 | 11.26 |
| Y | L2, L6, P2 | 2330 | 11.26 |
| B | L3, L4, P3 | 2300 | 11.11 |
Connected load = 960 W light + 6000 W power = 6960 W
Most loaded phase = 2330 W
Iph = 2330 / (230 × 0.9) = 11.26 A
Main MCB ≥ 1.25 × 11.26 = 14.07 A → 16 A TPN MCB
DB specification: 4-way-per-phase TPN DB (12 ways in all, spares included) with 16 A TPN MCB as incomer, 25 A 4-pole RCCB (100 mA) for earth-leakage protection, 6 A SP MCBs (B-curve) for light circuits and 20 A SP MCBs for power circuits. Incoming cable: 4-core 1.5 mm² Cu PVC (rating 21 A ≥ 16 A), plus earth continuity conductor.
3-phase, 400/230 V, 4-wire supply
|
[Energy meter]
|
[16 A TPN MCB]
|
[25 A 4P RCCB]
|
==R====Y====B====N== busbars
| | | | |
L1 L2 L3 P1 P2 ...
Wiring layout
20 m
+-----------------------------------+
| x x x x x x x x [P]|
| x x x x x x x x | 10 m
| x x x x x x x x [P]|
| x x x x x x x x |
+[P]-----[P]----[SB][DB]-------[P]--+
door
x = 30 W luminaire [P] = 16 A socket
Conduit runs along rows; each row-group
is looped back to its switch on SB.
Wiring is in concealed PVC conduit: 1.5 mm² Cu (phase, neutral, earth) for light circuits and 2.5 mm² Cu for socket circuits, all drawn from the DB near the door.
Distribution system layout
NEA LT supply 400 V, 3φ 4-wire
|
[Energy meter] → [Main switch / TPN MCB]
|
Office DB (TPN) ── L circuits → luminaires
└─ P circuits → sockets
|
Earth electrode (pipe/plate) ── ECC to all points
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Drawing hall 40 × 25 × 6 m, 250 lux LED · Industrial Power Distribution and Illumination, chapter 7 · asked 3×
- Conference hall 2×36 W CFL lighting · Industrial Power Distribution and Illumination, chapter 7
- Flood lighting design and luminaire selection · Industrial Power Distribution and Illumination, chapter 8
- Ten factors for flood, street lighting, luminaires · Industrial Power Distribution and Illumination, chapter 8
- Room 40 × 15 m, 75 lux FTL design · Industrial Power Distribution and Illumination, chapter 7
- Factory hall 55.75 m × 40.25 m LED lighting · Industrial Power Distribution and Illumination, chapter 7 · asked 4×
- Nichrome strip resistor length and width · Electric Machine Design, chapter 2 · asked 2×
- Crest width, cistern length of vertical drop, Q 1.55 · Irrigation and Drainage Engineering, chapter 7 · asked 2×
- Field and office work; length of offsets · Surveying I, chapter 3
- Cluster analysis; K-means on height/width · Data Mining, chapter 5
All Industrial Power Distribution and Illumination chapter 7 questions →