Operating time of two relays (300/1, 6000 A)

Short answer

Relay 1: pickup 375 A, PSM=6000/375=16, t(TMS=1)=2.2 s, t1=0.2×2.2=0.44 s. Relay 2: pickup 450 A, PSM=6000/450=13.33, t(TMS=1)=2.8 s, required t2=0.44+0.3=0.74 s, TMS2=0.74/2.8=0.264.

The time multiplier setting of relay 1 is 0.2 and the time grading margin between the relays is 0.3 second. Determine the time of operation of two relays. [Figure: CB – CT 300/1 with Relay 2 (plug setting = 150%) – CB – CT 300/1 with Relay 1 (plug setting = 125%) – fault, IF = 6000 A.]

PSM23.659.2313.331620
Time in sec1063.92.92.82.22.1

Relay 1 (nearest the fault) operates first; relay 2 is the back-up and must operate 0.3 s after relay 1.

Data: CT 300/1 for both, plug setting R1 = 125%, R2 = 150%, TMS of R1 = 0.2, IF = 6000 A.

Relay 1

Pick-up current = 1.25 × 300 = 375 A
PSM = 6000/375 = 16
t(TMS=1) = 2.2 s (from table)
t1 = 0.2 × 2.2 = 0.44 s

Relay 2

Pick-up current = 1.5 × 300 = 450 A
PSM = 6000/450 = 13.33
t(TMS=1) = 2.8 s (from table)
t2 = t1 + margin = 0.44 + 0.3 = 0.74 s
TMS2 = 0.74 / 2.8 = 0.264
RelayPick-upPSMt at TMS=1TMSOperating time
1375 A162.2 s0.20.44 s
2450 A13.332.8 s0.2640.74 s

Answer: relay 1 operates in 0.44 s and relay 2 in 0.74 s (TMS of relay 2 ≈ 0.264).