- 2071 Bhadra · 6 marks
Isolator function and application
Short answer
An isolator is a no-load switch providing a visible break for safe isolation. It disconnects equipment after the circuit breaker opens, enabling maintenance. Applications include both sides of circuit breakers, line bays, bus sectionalizers, and transformer isolation.
What is an isolator? Write its function and application in power system.
An isolator (disconnector) is a mechanical switch that opens or closes a circuit only when no current, or negligible current, is flowing. It provides a visible, safe air gap between a live part and the part to be maintained. It has no arc-quenching arrangement, so it must never be opened on load.
Functions of an isolator
- Safety isolation: disconnects equipment (CB, transformer, line, bus section) from all live parts so maintenance can be done safely.
- Visible break: the open blades give an obvious, visible gap that confirms the circuit is dead.
- Sectionalising: divides a busbar or a feeder into sections so that one part can be taken out while the rest stays in service.
- Change-over / bus selection: in double-bus schemes, isolators select which bus a feeder is connected to.
- Earthing: many isolators are combined with an earth switch to earth the dead line and discharge trapped charge.
- Breaking small currents: can safely break the small charging current of busbars or short unloaded lines and the magnetising current of small transformers (where permitted).
Applications in power system
- On both sides of every circuit breaker in substations, so the CB can be maintained.
- At the incoming and outgoing line bays of substations (line isolator with earth switch).
- Bus coupler and bus sectionaliser isolators in single and double busbar arrangements.
- Transformer isolation on HV and LV sides of power and distribution transformers.
- Pole-mounted (gang-operated) AB switches on 11 kV and 33 kV distribution lines in Nepal for sectionalising feeders.
- Isolating potential transformers, lightning arresters and capacitor banks.
- Bypass isolators used to bypass a CB during maintenance.
Types (brief)
- By construction: double-break, single-break (centre-break), pantograph, vertical-break.
- By location: bus-side, line-side, transfer-bus isolators.
- By operation: manual (hook stick), gang-operated, motorised.
Example: in a 33/11 kV substation, the operator first opens the 33 kV breaker, then opens the isolators on both sides and closes the earth switch before work is done on the breaker.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolator in SLD; application of contactors · Switchgear and Protection, chapter 4
- Isolator construction, principle and application · Switchgear and Protection, chapter 4
- Isolator vs CB and why both used · Switchgear and Protection, chapter 4 · asked 4×
- Function of reactor in power system · Power Plant Equipment, chapter 4 · asked 3×
- Synchronizing power coefficient and application · Power System Analysis II, chapter 6
- Application, system and device domain · Multimedia System, chapter 1
- Short note: Application of queuing system · Simulation and Modeling, chapter 4