- 2070 Magh · 6 marks
Isolator in SLD; application of contactors
Short answer
In a substation single line diagram, isolators disconnect circuit breakers, lines, and transformers for maintenance, providing a visible break after the CB opens. Contactor applications include frequent motor starting, capacitor switching, lighting control, and remote automation, requiring fuse backup.
With reference to a single line diagram of a power system, discuss the function of isolator. Also mention the application of contactors in power system.
An isolator is an off-load switch that provides a visible break so that equipment can be safely separated from live parts after the circuit breaker has interrupted the current.
Function of isolator in a single line diagram
Incoming 132 kV line
|
[LI]--ES LI = line isolator + earth switch
|
[CB1]
|
[BI] BI = bus isolator
|
=======+========[BS]========= 132 kV bus
| sectionaliser
[BI]
|
[CB2]
|
[TI]
|
( T/F ) 132/33 kV
|
...
- Isolation of CB: isolators BI and LI on both sides of CB1 allow the breaker to be taken out for maintenance. Sequence: open CB1 → open LI and BI → close ES.
- Line isolation and earthing: the line isolator with earth switch earths the incoming line during line work and discharges trapped charge.
- Bus sectionalising: isolator BS divides the bus into two sections, so one half can be maintained while supply continues from the other.
- Transformer isolation: TI isolates the transformer after its breaker opens.
- Bus selection: in double-bus arrangements, isolators transfer a feeder from main to reserve bus.
- Visible open gap for confirming safe working conditions.
Isolators are interlocked so they can be operated only when the related CB is open.
Application of contactors in power system
A contactor is an electromagnetically operated switch for frequent on-load switching of normal currents. Applications:
- Motor starters: DOL, star-delta, reversing and auto-transformer starters for pumps, fans, compressors and conveyors.
- Capacitor bank switching in automatic power factor correction (APFC) panels.
- Lighting control: street lighting with timers or photocells, large building lighting.
- Heating loads: furnaces, ovens and heaters controlled by thermostats.
- Automatic transfer switches (ATS) between mains and diesel generator.
- Remote and automatic control with PLCs, level switches and pressure switches (e.g. water pumping stations).
- Auxiliary supply in substations and battery charger switching.
- No-volt and overload protection of motors together with overload relays and back-up fuses.
Unlike isolators, contactors switch load current many times a day; unlike CBs, they cannot interrupt short-circuit currents and need fuse or MCCB back-up.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Isolator function and application · Switchgear and Protection, chapter 4
- Isolator construction, principle and application · Switchgear and Protection, chapter 4
- Isolator operation with CB in HV installation · Switchgear and Protection, chapter 4
- Isolator vs CB and why both used · Switchgear and Protection, chapter 4 · asked 4×
- Single line diagram and its significance · Power System Analysis I, chapter 3
- Interconnected system SLD with bus voltages · Power System Analysis I, chapter 1
- Single line diagram from 11 kV to end use · Industrial Power Distribution and Illumination, chapter 4 · asked 3×
- Interconnected system SLD and functions of each part · Power System Analysis I, chapter 1