- 2073 Magh · 4 marks
Methods of providing backup protection
Short answer
Remote back-up uses upstream time-graded relays; relay back-up duplicates independent relays at the same station; breaker back-up (breaker failure) trips all breakers on the bus if a breaker fails; centrally coordinated back-up uses station computers.
State the various methods used to provide backup protection.
Back-up protection operates, after a time delay, only when the primary protection or its breaker fails to clear a fault. The common methods are:
- Remote back-up: relays at the adjacent (upstream) station act as back-up. They see the fault but are time-graded so that the primary relay has the first chance.
- Example: zone-2 and zone-3 of a distance relay, or a time-graded IDMT relay at the source end.
- Independent of the primary station's CTs, DC supply and breaker, so very reliable; but it is slow and disconnects a larger part of the system.
- Relay back-up (local duplication): a second, independent relay at the same station (preferably a different principle, fed from separate CT cores and DC supply) trips the same breaker. Example: main-1 and main-2 distance relays on EHV lines.
- Breaker back-up (breaker failure protection): if the breaker does not open within a set time (about 150–200 ms) after the trip signal while current still flows, the breaker-failure relay trips all other breakers on the same bus that feed the fault.
- Centrally coordinated back-up: in modern substations with a central computer, the system state is monitored and, on failure of primary protection, the most suitable breakers are tripped.
A B C
─[CB1]────┼──[CB2]────┼── F
R1 (remote back-up) R2 primary + local
BF relay trips bus B
Usually remote back-up is used on distribution systems and local relay + breaker back-up on EHV systems.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Primary and backup protection · Switchgear and Protection, chapter 1 · asked 3×
- Zones and backup for breaker 7 failure · Switchgear and Protection, chapter 1
- Isolator vs CB and why both used · Switchgear and Protection, chapter 4 · asked 4×
- Comparators used in static relays · Switchgear and Protection, chapter 8 · asked 2×
- Contactor for motor control and protection · Switchgear and Protection, chapter 4 · asked 3×
- Snubber circuit and dv/dt protection · Power Electronics, chapter 1 · asked 2×
- Series regulator stability factor and overload protection · Electronics Devices and Circuit, chapter 6
- Retaining and slope protection structures · Transportation Engineering I, chapter 5
- Earthing for shock protection and methods · Industrial Power Distribution and Illumination, chapter 2