- 2075 Bhadra · 6 marks
Protection requirements; protective system vs scheme
Short answer
Basic requirements: selectivity, speed, sensitivity, reliability, stability, simplicity, economy, adequateness. A protective system performs one function using a single principle (e.g., differential), while a protective scheme is the coordinated arrangement for an element, comprising multiple systems plus breakers.
What are the basic requirements of protection scheme? Differentiate between a protective system and protective scheme.
Basic requirements of a protection scheme
- Selectivity: only the faulty section is disconnected by the nearest breakers.
- Speed: the fault is cleared quickly to limit damage and preserve stability.
- Sensitivity: operates for the minimum fault current (high-resistance faults, minimum generation).
- Reliability: operates whenever required (dependability) and never wrongly (security).
- Stability: stays inactive for through-faults, load swings and transformer inrush.
- Simplicity and economy: cost proportional to the importance of the equipment; easy to maintain.
- Adequateness: covers all likely faults and abnormal conditions of the equipment.
Protective system vs protective scheme
A protective system is a complete arrangement of protection equipment and associated devices that performs one specified protective function, based on one protection principle. It includes the relay(s), CTs and VTs, wiring, trip circuit, auxiliary DC supply and, where used, the communication channel (by the IEC definition the circuit breaker itself is excluded). Example: the distance protection system of a line, or the differential protection system of a transformer. If any of its components fails, that protection fails.
A protective scheme is the coordinated arrangement of protection for one or more elements of the power system. It includes all the equipment needed to make the protection work (relays, CTs, VTs, circuit breakers, batteries) and may comprise several protective systems. Example: the protection scheme of a power transformer = differential system + restricted earth-fault system + Buchholz and temperature devices + back-up overcurrent/earth-fault system, all tripping the HV and LV breakers.
| Point | Protective system | Protective scheme |
|---|---|---|
| Meaning | Arrangement that performs one protection function | Coordinated arrangement protecting a whole element (or elements) |
| Based on | One protection principle (distance, differential, overcurrent) | Several principles combined (main + back-up) |
| Contents | Relay, CT/VT, wiring, trip circuit, DC supply, communication channel | Several protective systems plus circuit breakers and all supporting equipment |
| Scope | Narrower; a part of a scheme | Wider; may comprise several systems |
| Example | Distance relay + CTs + CVT + DC supply + trip circuit of a line | Complete line protection: main-1 and main-2 distance, back-up overcurrent, breaker-failure, auto-reclose |
Protective scheme of a transformer
┌───────────────────────────────────────┐
│ Differential system (CTs + 87T relay) │
│ REF system (CTs + 64R relay) │
│ Buchholz / temperature devices │──► trip HV & LV CBs
│ Back-up O/C & E/F (CTs + 51/51N) │
│ Common DC supply and trip circuits │
└───────────────────────────────────────┘
each row = one protective system
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Basic requirements of a protection scheme · Switchgear and Protection, chapter 1 · asked 3×
- Requirements, coordination and protection zone · Switchgear and Protection, chapter 1
- Unit protection scheme · Switchgear and Protection, chapter 7
- Converting IDMT scheme to differential protection · Switchgear and Protection, chapter 7
- Knee point voltage; measuring vs protective CT · Switchgear and Protection, chapter 2
- T/F: protection ratio vs system voltage · Transmission and Distribution System Design, chapter 3
- Basic requirements of classification · Soil Mechanics, chapter 3 · asked 2×
- Basic requirements of linear programming · Project Engineering, chapter 3
- Mutex requirements; token vs non-token · Distributed System, chapter 6