Knee point voltage; measuring vs protective CT

Short answer

Knee point voltage is where a 10% rise in secondary emf causes 50% rise in exciting current, indicating saturation. Meeasuring CTs have low knee point, saturate early to protect meters; protective CTs have high knee point to avoid saturation during faults, ensuring accurate relay current.

What is 'knee point voltage'? Mention the difference between measuring and protective CT.

Knee point voltage

The knee point voltage of a CT is the point on its excitation (magnetisation) curve where a 10 % increase in secondary e.m.f. causes a 50 % increase in exciting current (IEC/IS definition). Beyond this point the core saturates, the exciting current rises rapidly and the CT can no longer reproduce the primary current faithfully.

 Vs (sec. emf)
  │            ___________ saturation
  │        _--
  │   Vk ●   knee point
  │     /
  │    /  linear region
  │   /
  └──┴────────────────── Ie (exciting current)

A protective CT needs a high knee point voltage so that it does not saturate during heavy fault current; it is chosen so that Vk ≥ K × If(sec) × (R_CT + R_lead + R_relay).

Measuring CT vs protective CT

PointMeasuring CTProtective CT
PurposeFeeds meters (ammeter, energy meter)Feeds relays
Working rangeUp to about 120 % of rated currentUp to 10–30 times rated current
Accuracy neededHigh at normal current (class 0.1, 0.2, 0.5, 1)Moderate, maintained up to fault current (5P, 10P, PS)
Knee pointLow – saturates earlyHigh – no saturation during faults
CoreSmall, high-permeability (nickel-iron)Large cross-section, CRGO steel
SaturationDesirable: protects meters during faultsUndesirable: relay must see the fault
Instrument security factorLow (ISF ≤ 5)Accuracy limit factor 10, 15, 20, 30