- 2080 Chaitra · 5 marks
Knee point voltage and CT errors
Short answer
Knee point voltage is the secondary e.m.f. at which a 10% increase causes a 50% rise in exciting current, marking the onset of saturation. CT errors include ratio error due to the loss component of exciting current, phase angle error from the magnetizing component, and composite error. High burden, saturation, and remanent flux are key causes.
What do you mean by typical knee point voltage in relation to CT? Briefly explain the different errors of CT and its causes.
Typical knee point voltage
The knee point voltage (Vk) of a CT is the secondary e.m.f. at which a 10 % rise in voltage causes a 50 % rise in exciting current. It is the boundary between the linear part of the excitation curve and saturation.
Vs │ ______ saturation
│ Vk ●
│ /
│ / linear (accurate) region
└──────/──────────────── Ie
- Below Vk the CT transforms current accurately; above it the core saturates and secondary current is distorted and reduced.
- A protective CT must have Vk higher than the voltage needed to drive the maximum fault current through its burden: Vk ≥ K·I_f(sec)·(R_ct + R_lead + R_relay). Typical values are a few hundred volts for protection CTs and much lower for metering CTs.
Errors of CT and their causes
An ideal CT has I_s = I_p / K_n exactly in phase opposition. In practice part of the primary ampere-turns is used to supply the exciting current I₀, causing errors.
- Ratio (current) error: difference between actual and nominal ratio,
Current error % = (K_n·I_s − I_p) / I_p × 100Cause: the loss component of I₀ (in phase with I_s) reduces I_s; also burden power factor. - Phase angle error (phase displacement, β): angle between the primary current and the reversed secondary current. Cause: the magnetising component of I₀ (in phase with flux) makes I_s lag/lead the ideal phasor.
- Composite error: r.m.s. value of the difference between ideal and actual secondary current over a cycle, including harmonics caused by saturation (important for protective CTs).
Causes and factors increasing errors
- High exciting current due to poor core material or high flux density.
- High burden (impedance of relays + leads) – requires more e.m.f., more flux, more I₀.
- Burden power factor (inductive burden increases ratio error; resistive increases phase error).
- Saturation due to high fault current or DC offset; remanent flux in core.
- Low primary current (operating near ankle region, low permeability).
- Frequency different from rated.
Errors are reduced by using high-permeability cores (CRGO, nickel-iron), low flux density, low burden and turn compensation.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Knee point voltage; measuring vs protective CT · Switchgear and Protection, chapter 2
- Knee point voltage and CT selection · Switchgear and Protection, chapter 2
- Different errors of CT · Switchgear and Protection, chapter 2
- Need of instrument transformers; CT errors · Switchgear and Protection, chapter 2
- CT purpose, phasor diagram and errors · Switchgear and Protection, chapter 2
- Causes of PT ratio and phase errors · Switchgear and Protection, chapter 2
- Typical voltage levels and why three-phase · Power System Analysis I, chapter 1
- Typical power system with voltage levels · Power System Analysis I, chapter 1
- Parseval's relation for CT periodic signals · Signals and Systems, chapter 2 · asked 4×