CT purpose, phasor diagram and errors
Short answer
A CT steps down high line current for safe measurement and relaying, providing isolation. Ratio error is the percentage difference between nominal and actual ratios, caused by the loss component of exciting current. Phase angle error is the small angle β between primary current and reversed secondary current, due to the magnetizing component.
What is the purpose of a CT? Draw a phasor diagram and explain briefly what are the ratio and phase angle error of CT?
Purpose of a CT
A current transformer steps down a high line current to a standard low value (1 A or 5 A) for meters and relays, and isolates them from the high-voltage circuit, so that standard low-rated instruments can be used safely.
Phasor diagram of CT
Flux Φ is the reference (horizontal).
−E_s −n·I_s
▲ ▲ ▲ I_p
│ δ ╱ β ╱
│ ╱ ╱
│ ╱ ╱
│ ╱ ╱
│ ╱ ╱ _ ─▶ I₀
│╱ ╱_ ─ α
O──────────────────► Φ
I_m = I₀ cos α (along Φ), I_w = I₀ sin α (⊥ Φ)
E_s lags Φ by 90°; I_s lags E_s by δ.
I_p = (−n·I_s) + I₀ (phasor sum)
Where: Φ = core flux, E_s = secondary induced e.m.f., I_s = secondary current (lags E_s by the burden angle δ), −n·I_s = reversed secondary current referred to the primary, I₀ = exciting current, leading Φ by α, = I_m (magnetising, in phase with Φ) + I_w (loss, leading Φ by 90°), n = turns ratio N_s/N_p.
The primary current I_p is the phasor sum of the reversed secondary current (n·I_s) and the exciting current I₀. Because of I₀, I_p is neither exactly n·I_s in magnitude nor exactly in phase with it; the reversed secondary current leads I_p by the small angle β.
Ratio error
The actual ratio R = I_p/I_s differs from the nominal ratio K_n:
R ≈ n + I₀ sin(δ + α) / I_s
Ratio error (%) = (K_n − R) / R × 100
It arises mainly from the loss component of I₀ and depends on the burden.
Phase angle error
β is the angle between I_p and the reversed I_s:
β ≈ (180/π) · I₀ cos(δ + α) / (n·I_s) degrees
It arises mainly from the magnetising component I_m. It is important for wattmeters, energy meters and directional relays.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Causes of PT ratio and phase errors · Switchgear and Protection, chapter 2
- Knee point voltage and CT errors · Switchgear and Protection, chapter 2
- Different errors of CT · Switchgear and Protection, chapter 2
- Need of instrument transformers; CT errors · Switchgear and Protection, chapter 2
- CT ratio for 33/6.6 kV star/delta (300:5) · Switchgear and Protection, chapter 7
- CT ratio for 33/6.6 kV star/delta (400/5) · Switchgear and Protection, chapter 7
- Phase diagram; void ratio, saturation · Soil Mechanics, chapter 2
- Salient pole generator phasor diagram in per unit · Electric Machines II, chapter 1
- Three-phase connections and series RC phasor · Fundamental of Electrical and Electronics Engineering, chapter 3
- Thread errors and effect of pitch error · Metrology, chapter 12