Substation protection against direct strokes

Short answer

Substations are protected from direct strokes by earthing screens (wire mesh over equipment), overhead shield wires extended from lines, and lightning masts, all bonded to a low-resistance earth mat. These intercept strokes and conduct current to earth. Protective zones are verified by angle or rolling-sphere methods. Arresters at line entrances complement this by clamping travelling waves.

Describe the protection of stations and sub-stations against direct lightning strokes.

Stations and substations contain costly equipment (transformers, breakers, busbars), so a direct lightning stroke must be intercepted before it reaches live parts and conducted to earth through a path of low impedance. The common methods are earthing screens, overhead shield wires and lightning masts, all bonded to the station earth mat.

1. Earthing screen

   ==+=====+=====+=====+==   earthed wire mesh
     |     |     |     |     above equipment
  [T/F]  [CB]  [Bus] [CT]
     |     |     |     |
  ======== earth mat ========
  • A network (mesh) of copper or galvanised steel wires is erected over the whole substation on the steel structures.
  • It is connected at many points to the low-resistance earth mat of the substation.
  • A direct stroke hits the screen instead of the equipment and the current flows to earth.
  • Advantages: simple and cheap; covers the whole yard.
  • Limitations: it does not protect against travelling waves entering through incoming lines; if the earth resistance is high, the potential of the screen rises and can cause back flashover to equipment.

2. Overhead ground wires extended over the station

  • The shield wires of incoming lines are carried over the substation and earthed on the gantries.
  • Equipment lies within the protective zone (shielding angle of about 30°–45° under the wire).

3. Lightning masts / spikes

  • Tall earthed steel masts or spikes on gantries (Franklin rods) placed so that all equipment is within the cone or rolling-sphere protection zone.
  • Each mast has its own earth connection bonded to the earth mat.

Design points

  1. Earth mat resistance should be low (typically below 1 Ω for large substations).
  2. Adequate clearance between shield wires/masts and live parts to avoid back flashover.
  3. Down conductors short and straight to reduce inductance.
  4. Protective zone checked by the protective-angle or rolling-sphere method.

Protection against direct strokes is always used with lightning arresters at line entrances and transformer terminals, which protect against surges travelling in along the lines.