- 2077 Chaitra · 4 marks
Need of VT and CCVT construction
Short answer
Voltage transformers provide isolated, standard-level voltage to protection relays like distance and directional types and supply residual voltage for earth-fault detection. A CCVT comprises a capacitor divider, a tuning reactor resonating at 50 Hz to compensate source impedance, an intermediate VT for 110/√3 V output, a ferro-resonance suppressor, and a drain coil for carrier signals.
Why voltage transformers are required in protection system? Also describe the construction of CCVT.
Why voltage transformers are required in protection
A voltage (potential) transformer reduces the system voltage to a standard value (110 V line or 110/√3 V phase) for relays and meters.
- Many relays need voltage as an input: distance (impedance) relays, directional overcurrent and directional earth-fault relays, under/over-voltage relays, under/over-frequency relays, reverse power and loss-of-excitation relays, and synchronism-check relays.
- Relays cannot be connected directly to 11 kV–400 kV lines; the VT gives isolation and safety.
- Standard low-voltage relays can be used for any system voltage.
- Open-delta VT connection provides the residual voltage (3V₀) for earth-fault detection and directional earth-fault relays.
Construction of CCVT (coupling capacitor voltage transformer)
HV line
│
═╪═ C1 ┐
│ │ capacitor stack in
═╪═ C2 ┘ porcelain housing
├──── tap V₂ (≈10–20 kV)
│ │
│ [L] tuning reactor
│ │
│ ┌─┴──┐
│ │IVT │→ 110/√3 V to relays
│ └────┘ + ferro-resonance damper
[Drain coil]──► PLC carrier equipment
│
═══ earth
- Capacitor divider: series-connected oil-impregnated capacitor elements (C1 high-voltage part, C2 low-voltage part) in a porcelain/polymer column. Tap voltage = V × C1/(C1 + C2).
- Tuning reactor (L): in series with the IVT primary; resonates with C1 + C2 at 50 Hz (ωL = 1/ω(C1+C2)) so the ratio and phase do not change with burden.
- Intermediate VT: small oil-immersed transformer stepping the tap voltage to the standard secondary.
- Ferro-resonance suppression circuit across the secondary.
- Drain coil and carrier terminal: low impedance at 50 Hz, high at carrier frequency; allows the capacitor stack to couple PLC signals to the line (hence "coupling capacitor").
- Oil-filled base tank with terminal box and protective spark gap.
CCVTs are used at 66 kV and above because they are cheaper than electromagnetic VTs and also serve carrier communication.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Need of instrument transformers; CT errors · Switchgear and Protection, chapter 2
- Need of capacitive voltage transformer · Switchgear and Protection, chapter 2
- Construction of capacitor voltage transformer · Switchgear and Protection, chapter 2
- Need for protection and causes of faults · Switchgear and Protection, chapter 1
- Protection requirements; protective system vs scheme · Switchgear and Protection, chapter 1
- Lightning protection schemes · Switchgear and Protection, chapter 5
- T/F: protection ratio vs system voltage · Transmission and Distribution System Design, chapter 3
- Need and conditions for parallel operation of transformers · Electrical Machines I, chapter 2
- T/F: single phase transformers for lower utilization voltage · Transmission and Distribution System Design, chapter 7
- LV voltage of Δ–Y bank of 100 kVA transformers · Electrical Machines I, chapter 2