Short answer

RMS output voltage is V_s sqrt((1/pi)(pi - alpha + sin(2 alpha)/2)). In micro hydro ELC, the controller senses frequency and adjusts alpha to vary dump load power, keeping total load constant.

Explain the operation single phase AC voltage controller. Derive the expression for RMS value of the output voltage. How it can be used on ELC of MHP scheme?

A single-phase AC voltage controller varies the rms value of the AC voltage applied to a load, at the supply frequency, by delaying the firing of two anti-parallel thyristors (phase angle control).

Circuit and operation

        T1 --->|---
   +---|          |----+
   |    ---|<---  |    |
   |       T2          |
 ( ~ ) vs              R   vo
   |                   |
   +-------------------+
  1. 0<ωt<α0 < \omega t < \alpha: T1 not yet fired, vo=0v_o = 0.
  2. At α\alpha: T1 fired, vo=vsv_o = v_s until π\pi, where the current falls to zero and T1 turns off (natural commutation).
  3. π<ωt<π+α\pi < \omega t < \pi + \alpha: vo=0v_o = 0.
  4. At π+α\pi + \alpha: T2 fired, vo=vsv_o = v_s until 2π2\pi.
 vo     .
        | \
 -------|--\--------.------
 0      a   pi      |    / 2pi
                    |  /
                    |/
                   pi+a

RMS output voltage

Vo=[22π∫απVm2sin⁡2ωt  d(ωt)]1/2=[Vm22π{ωt−sin⁡2ωt2}απ]1/2=Vm2[1π(π−α+sin⁡2α2)]1/2\begin{aligned} V_o &= \left[\frac{2}{2\pi}\int_{\alpha}^{\pi} V_m^2\sin^2\omega t\; d(\omega t)\right]^{1/2} \\ &= \left[\frac{V_m^2}{2\pi}\left\{\omega t - \frac{\sin 2\omega t}{2}\right\}_{\alpha}^{\pi}\right]^{1/2} \\ &= \frac{V_m}{\sqrt{2}}\left[\frac{1}{\pi}\left(\pi - \alpha + \frac{\sin 2\alpha}{2}\right)\right]^{1/2} \end{aligned} Vo=Vs1π(π−α+sin⁡2α2)V_o = V_s\sqrt{\frac{1}{\pi}\left(\pi - \alpha + \frac{\sin 2\alpha}{2}\right)}

As α\alpha goes from 0 to π\pi, VoV_o goes from VsV_s to 0, and load power Vo2/RV_o^2/R from full to zero.

Use in the ELC of a micro hydro (MHP) scheme

Micro hydro plants usually run with a fixed water input and no mechanical governor. The electronic load controller (ELC) keeps the total electrical load constant:

Pgen=Pconsumer+Pdump=constantP_{gen} = P_{consumer} + P_{dump} = \text{constant}
 Gen ---+-------> Consumers
        |
        +--[ AC voltage controller ]--> Dump heater
        |            ^ alpha
        +-> sense f/V -> controller
  • The controller senses generator frequency (or voltage).
  • Consumer load decreases → frequency tends to rise → α\alpha is reduced → more power to the dump (ballast) heater.
  • Consumer load increases → α\alpha is increased → less power to the dump load.
  • So speed, frequency and voltage stay nearly constant without a governor.
  • The dump load is usually water or air heaters, and the heat can be used.

Drawbacks of phase control here are harmonics and poorer power factor at mid-range α\alpha; binary-weighted dump loads or integral cycle control reduce this.

✓ Answer checked by Claude Opus 5.5 (high effort)