Reverse power flow in bipolar HVDC link
Short answer
Both converters are fully controlled, with V_d = V_do cos α. In normal mode, α1<90° (rectifier) and α2>90° (inverter); reversal makes α1>90° and α2<90°, reversing voltage polarity while current direction stays same. For current flow, α1+α2<180°, and for low resistance, α2≈180°–α1.
With mathematical aid, explain how full converters can be used for reverse power flow in bipolar link of HVDC transmission.
In a bipolar HVDC link, each end has two fully controlled (thyristor) converters in series with the mid-point earthed; one pole is at and the other at . Because a full converter can work as a rectifier () or as an inverter (), power flow is reversed simply by changing the firing angles at both ends; the current direction cannot change, so the pole voltages reverse.
Bipolar link
Station 1 Station 2
[Conv 1P] +Vd ======Id=====> [Conv 2P]
| |
earth earth
| |
[Conv 1N] -Vd <=====Id====== [Conv 2N]
Each pole forms a link like the following (one pole shown):
AC sys 1 AC sys 2
| Conv 1 R, Ld Conv 2 |
+--[3-ph full]--+--/\/\--+--[3-ph full]--+
bridge Vd1 (+) Id -> (+) Vd2' bridge
| |
+---------------+
Vd1 = Vdo cos a1 Vd2' = -Vdo cos a2
Mathematical analysis
Let both converters have the same no-load voltage and the line resistance be . Converter 1 gives . Converter 2 is connected in opposition, so its terminal voltage seen by the line is . Thyristors allow current in one direction only:
Power sent by converter 1 and received by converter 2:
Case 1: power from system 1 to system 2.
- : converter 1 is a rectifier (, ).
- : converter 2 is an inverter (, delivered to system 2).
- Line voltage is positive at the top conductor.
Case 2: power from system 2 to system 1 (reversal).
- Make : converter 1 becomes an inverter ().
- Make : converter 2 becomes a rectifier.
- The current direction stays the same; only the polarity of the DC line voltage reverses, so changes sign.
Condition for current flow in both cases:
For a line of small resistance, is small, so
The magnitude of (and power) is set by how much is less than ; the direction of power is set by which converter has .
| Mode | Line polarity | Power | ||
|---|---|---|---|---|
| Normal | (rectifier) | (inverter) | + | 1 → 2 |
| Reversed | (inverter) | (rectifier) | − | 2 → 1 |
In the bipolar link
- Both poles are controlled together. In normal mode the upper pole is and the lower ; on reversal both polarities swap (upper becomes , lower ), while the pole currents keep their directions.
- Total power reverses with no mechanical switching.
- In practice, the rectifier controls current (constant current) and the inverter controls extinction angle ( control); reversal is done by ramping current to a low value, reversing the voltage by changing , then raising current.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Reversible HVDC power flow: firing angle relation · Power Electronics, chapter 7
- Why HVDC over HVAC: mathematical comparison · Power Electronics, chapter 7 · asked 4×
- HVDC advantages; negative polarity in homopolar link · Power Electronics, chapter 7
- HVDC advantages and power transfer capacity · Power Electronics, chapter 7 · asked 2×
- When HVDC is economical; equal transmission capacity · Power Electronics, chapter 7
- Series full converters: rectification and inversion · Power Electronics, chapter 2 · asked 4×
- Numerical: reverse link distance by link budget · Wireless Communication, chapter 3
- FACTS and HVDC for Nepal's power industry · High Voltage Engineering, chapter 1
- T/F: HVDC converter reactive power need · Transmission and Distribution System Design, chapter 1
- Short note: reverse or tidal flow operation · Transportation Engineering II, chapter 1