T/F: HVDC converter reactive power need

Short answer

True. Line-commutated converters draw lagging current due to firing and commutation angles, consuming reactive power up to 50–60% of real power. Converter stations need large shunt capacitor banks, filters, or SVCs to supply this support.

State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: HVDC converter station requires huge amount of reactive power support.

TRUE.

  • Line-commutated (thyristor) converters always draw current that lags the voltage, both as rectifier (firing angle α\alpha) and as inverter (extinction angle γ\gamma), plus extra lag due to commutation overlap μ\mu.
  • The reactive power consumed is roughly Q≈Ptan⁡ϕQ \approx P\tan\phi with cos⁡ϕ≈12[cos⁡α+cos⁡(α+μ)]\cos\phi \approx \frac{1}{2}[\cos\alpha + \cos(\alpha+\mu)]; in practice QQ is 50–60% of the transmitted real power at each end.
  • This reactive power is supplied by AC filters (which also remove harmonics), shunt capacitor banks, synchronous condensers or SVC/STATCOM at the converter station.

So a 1000 MW HVDC terminal needs about 500–600 MVAr of local reactive support. (Voltage-source converter HVDC does not have this need, but the statement refers to conventional HVDC.)