T/F: LLF unity for constant power loss

Short answer

TRUE. For constant power loss (e.g., transformer core loss, dielectric loss), average loss equals peak loss, so LLF = 1. These losses depend on nearly constant voltage, not load current.

State whether the following statement is TRUE or FALSE. Justify your answer with a brief explanation: Loss of load factor (LLF) is always unity while evaluating energy loss from constant power loss.

TRUE.

Loss of load factor is defined as

LLF=Average power loss over periodPeak power lossLLF = \frac{\text{Average power loss over period}}{\text{Peak power loss}}

If the power loss is constant throughout the period, the average loss equals the peak loss, so LLF=1LLF = 1.

Justification:

  • Constant (no-load) losses such as transformer core (iron) loss, dielectric loss in cables, corona loss in fair weather and losses in meter potential coils depend on voltage, not on load current. Since voltage is nearly constant, these losses are the same every hour.
  • Their energy loss is therefore E=Pconst×8760E = P_{const} \times 8760 kWh/year, i.e. the loss acts at its full value for all hours (LLF = 1).
  • Example: a 100 kVA transformer with 200 W core loss loses 0.2×8760=17520.2 \times 8760 = 1752 kWh/year whether it is lightly or fully loaded.
  • Only variable (copper) losses, which vary as I2I^2, need LLF<1LLF < 1, e.g. LLF=0.3LF+0.7LF2LLF = 0.3LF + 0.7LF^2.

The statement also follows from the formula: a constant load gives LF=1LF = 1, and 0.3(1)+0.7(1)2=10.3(1) + 0.7(1)^2 = 1.