Short answer

Energy loss depends on load factor via the loss factor LLF, which ranges between LF² and LF (empirically LLF = 0.3LF + 0.7LF²). Percent energy loss = percent peak loss × (LLF/LF); lower LF reduces energy loss percentage.

Explain the dependency of energy loss computation in a transmission/distribution line on the load factor with proper mathematical aid.

Energy loss in a line depends on how the load varies with time, not just on the peak. Since copper loss is proportional to the square of current, the energy loss is linked to the load factor (LF) through the loss of load factor (LLF).

Definitions

For a line of resistance RR (per phase) carrying load P(t)P(t) at voltage VV and power factor cos⁡ϕ\cos\phi:

Ploss(t)=3I2R=P(t)2RV2cos⁡2ϕ=k P(t)2Eloss=∫0TkP(t)2dt=kPmax2 T⋅1T∫0T(PPmax)2dt⏟LLF\begin{aligned} P_{loss}(t) &= 3 I^2 R = \frac{P(t)^2 R}{V^2 \cos^2\phi} = k\,P(t)^2 \\ E_{loss} &= \int_0^T k P(t)^2 dt = k P_{max}^2 \, T \cdot \underbrace{\frac{1}{T}\int_0^T \left(\frac{P}{P_{max}}\right)^2 dt}_{LLF} \end{aligned}

So Eloss=Ploss,peak×LLF×TE_{loss} = P_{loss,peak} \times LLF \times T, and LF=1T∫0TPPmaxdtLF = \dfrac{1}{T}\int_0^T \dfrac{P}{P_{max}} dt.

Limits of LLF in terms of LF

Consider a two-step load: PmaxP_{max} for time tt and PminP_{min} for the rest (T−t)(T - t).

  • Case 1, Pmin=0P_{min} = 0: LF=t/TLF = t/T and LLF=t/TLLF = t/T, so LLF=LFLLF = LF (upper limit).
  • Case 2, very short peak (t→0t \to 0), off-peak PminP_{min} for nearly all the time: LF≈Pmin/PmaxLF \approx P_{min}/P_{max} and LLF≈(Pmin/Pmax)2LLF \approx (P_{min}/P_{max})^2, so LLF=LF2LLF = LF^2 (lower limit).

Hence

LF2≤LLF≤LFLF^2 \le LLF \le LF

Real load curves lie between these, giving the empirical relation (Buller–Woodrow):

LLF=0.3 LF+0.7 LF2LLF = 0.3\,LF + 0.7\,LF^2

Dependency of % energy loss on LF

%Eloss=Ploss,peak×LLF×TPmax×LF×T×100=%Ploss,peak×LLFLF\%E_{loss} = \frac{P_{loss,peak} \times LLF \times T}{P_{max} \times LF \times T} \times 100 = \%P_{loss,peak} \times \frac{LLF}{LF}

With the empirical formula, LLFLF=0.3+0.7 LF\dfrac{LLF}{LF} = 0.3 + 0.7\,LF.

Example: peak loss 8% of peak demand.

LFLLFLLF/LF% energy loss
0.30.1530.514.08%
0.50.3250.655.20%
1.01.01.08.00%

Conclusions:

  • For a given peak, a lower LF means fewer kWh lost but also fewer kWh sold; the % energy loss is always ≤ % peak power loss.
  • For a given energy delivered, a higher LF lowers the peak, and since loss ∝ peak², the absolute energy loss falls.
  • Energy loss can never be found by multiplying peak loss by hours; LLF must be used.
  • Constant losses (transformer core loss, corona) do not depend on load, so for them LLF = 1.