Load factor of two consumers
Short answer
Load factor = average load / maximum demand = energy/(max demand × hours). For A: 100 kWh/(20 kW×24 h) = 0.208; for B: 100 kWh/(5 kW×24 h) = 0.833. High load factor (B) means lower fixed cost per kWh for utility and lower demand charge for consumer, even with same energy use.
Define Load Factor. Consumer A has a load of 20 kW for 5 hrs and Consumer B has a load of 5 kW for 20 hrs. Find the load factor for both consumers and explain the significance of the load factor based on energy expenditure and utility point of view.
Load factor is the ratio of the average load to the maximum demand over a given period (day, month or year):
Load factor = Average load / Maximum demand
= Energy consumed / (Max demand × hours)
It is always ≤ 1 and shows how evenly the load is used.
Calculation (period = 1 day = 24 h)
Each consumer's maximum demand is its constant load.
Consumer A:
Energy = 20 kW × 5 h = 100 kWh
Avg load = 100 / 24 = 4.167 kW
LF(A) = 4.167 / 20 = 0.2083
Consumer B:
Energy = 5 kW × 20 h = 100 kWh
Avg load = 100 / 24 = 4.167 kW
LF(B) = 4.167 / 5 = 0.8333
Answer: Load factor of A = 0.208 (20.8%); load factor of B = 0.833 (83.3%).
Significance
Both consumers use the same energy, 100 kWh per day, but:
- Utility point of view: to supply A, the utility must keep 20 kW of generation, transformer and line capacity ready, which is used only 5 hours a day. For B only 5 kW of capacity is needed and it is used 20 hours. The fixed cost of plant per kWh sold is four times larger for A. So a high load factor (B) is better for the utility: plant is used well, cost per unit falls.
- Energy expenditure (consumer) point of view: under a two-part tariff (demand charge per kW + energy charge per kWh), A pays the same energy charge as B but four times the demand charge (20 kW vs 5 kW). A's cost per kWh is therefore higher. Improving load factor by spreading loads over time lowers the electricity bill.
- That is why utilities give lower rates to high load factor consumers and encourage off-peak use.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Optimum pf under two-part tariff (200 kW) · Industrial Power Distribution and Illumination, chapter 10
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- Load factor and demand factor numerical · Industrial Power Distribution and Illumination, chapter 1
- Aluminium cable for 25 kW single-phase load · Industrial Power Distribution and Illumination, chapter 5
- PF improvement of 490 kW load at 11 kV · Industrial Power Distribution and Illumination, chapter 10
- Substation capacity and diversity factor from load pattern · Industrial Power Distribution and Illumination, chapter 1
- Peak load, load factor and energy from load pattern · Transmission and Distribution System Design, chapter 6 · asked 2×
- 5th year peak load from consumer survey · Transmission and Distribution System Design, chapter 6 · asked 7×
- Dependency of energy loss on load factor · Transmission and Distribution System Design, chapter 6