Aluminium cable for 25 kW single-phase load
Short answer
Using voltage drop formula ΔV = I × ρ × 2L / A with 3% limit (6.6 V), load current 162.34 A, loop length 80 m, aluminium resistivity 0.0283 Ω·mm²/m, minimum area is 55.69 mm²; select 70 mm² aluminium cable (2.39% drop).
Calculate the cross-sectional area of Aluminum cable require to supply a single phase load of 25 KW at power factor of 0.7 lagging which is 40 m away from the voltage source so that voltage drop in the cable does not exceed 3% of the standard supply voltage of 220 V.
The cross-section is found from the permissible voltage drop of the go-and-return (2-wire) circuit.
Constants: resistivity of aluminium ρ = 0.0283 Ω·mm²/m (2.83 × 10⁻⁸ Ω·m); the whole I·R drop is taken (conservative, reactance neglected).
Load current I = P / (V × cosφ)
= 25000 / (220 × 0.7) = 162.34 A
Allowed drop = 3 % of 220 = 6.60 V
Loop length = 2 × 40 = 80 m
ΔV = I × R = I × ρ × 2L / A ≤ 6.60
A = ρ × 2L × I / ΔV
= 0.0283 × 80 × 162.34 / 6.60
= 55.69 mm²
Next standard size: 70 mm².
Check: ΔV = 0.0283 × 80 × 162.34 / 70
= 5.25 V (2.39 %) < 6.60 V OK
Answer: minimum area = 55.69 mm²; use a 70 mm² aluminium cable (drop 5.25 V). If only the in-phase component of drop (I·R·cosφ) is considered, A = 38.98 mm² and a 50 mm² cable would just satisfy the drop limit; the current rating of the chosen size must also be checked from the manufacturer's table for 162 A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Single-phase Cu cable for three loads · Industrial Power Distribution and Illumination, chapter 5
- Power/light sub-circuits and cable for 50 kW, 60 kW · Industrial Power Distribution and Illumination, chapter 5 · asked 4×
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- Cable size MDB to SDB1 (80 kW) and SDB2 (10 kW) · Industrial Power Distribution and Illumination, chapter 5 · asked 5×
- Cable size MDB to SDB1 (70 kW) and SDB2 (90 kW) · Industrial Power Distribution and Illumination, chapter 5 · asked 5×
- Cable size MDB to SDB-1 (60 kW) and SDB-2 (75 kW) · Industrial Power Distribution and Illumination, chapter 5 · asked 4×
- LT feeder options: loss and voltage drop, 50 kW · Transmission and Distribution System Design, chapter 7 · asked 3×
- LT loss and voltage drop, 60 kW four feeders · Transmission and Distribution System Design, chapter 7 · asked 3×
- Full converter, 25 A, α = 30°, input power factor · Power Electronics, chapter 2 · asked 4×
- Suspension 120 m: SF, BM at 25 m, cable area · Theory of Structures I, chapter 7
All Industrial Power Distribution and Illumination chapter 5 questions →